PLAN REVIEW COMMENTS
BUILDING DIVISION
(425) 771-0220
DATE: March 24, 2010
TO: Ron Johnson
ronmaile@verizon.net
FROM: Leif Bjorback, Assistant Building Official
RE: Plan Check: 2010-0168
Project: Hamburger Harrys Plumbing
th
Project Address: 610 5 Ave S
During review of the plans for the above noted project, it was found that the following information,
clarifications or changes are needed. Please provide written responses as to where the changes can
be found on the plans, and submit revised plans/documents to Theresa Umbaugh, Senior Permit
Coordinator. Thank you.
1.Please label on the plans which plumbing fixtures are new and which are existing.
2.Please indicate on the plans that an RPBA (reduced pressure backflow assembly) is required
at both soda dispensers, the glass washer and the ice maker.
3.An RPBA will be required on the coffee machine unless it will have an approved air gap.
4.Please indicate the type of backflow protection at the mop sink. This will need to be either
an RPBA, or a hose with air gap.
5.Provide specifications on the glasswasher. A Type 2 exhaust hood may be required
depending on the amount of heat and steam produced.