2010-0312 Lough Addition.pdf City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: May18, 2010 TO: Michael Lough nd 9623 232 St. SW mikelough@comcast.net FROM: Leif Bjorback, Assistant Building Official RE: Plan Check: 2010-0312 Project: Garage and Bonus Room Addition nd Project Address: 9623 232 St SW During review of the plans for the above noted project, it was found that the following information, clarifications or changes are needed. Please provide written responses as to where the changes can be found on the plans, and submit revised plans/documents to a Permit Coordinator. Thank you. 1.The maximum span of the 4x8 DF #1 floor beams is 8 feet. Please upsize the beams to 4x10 or show an additional post location under the Bonus Room to reduce the span. 2.The minimum size header over the garage door openings is 4x10. Please show this on the plan. 3.Braced wall lines are required at a maximum spacing of 25 feet in both directions. (There is an exception for one room up to 900 square feet to go up to 35 feet spacing, which in this case will apply to the garage.) A braced wall line will be required at the wall between the master bedroom and the bonus room. Please indicate how this “braced wall panel” will be constructed, as well as having a foundation wall below, which is required. R602.10.11 and R403.1.2 4.It appears that there are ABWP’s shown in locations where they are not required, specifically on the north and east exterior walls of the garage. These walls meet the prescriptive bracing requirements without the ABWP’s; therefore these (4) ABWP’s may be removed if you so choose. 5.Vertical rebar will be required unless the foundation and footings are placed in a monopour. The rebar would be 48 inches on center with a standard hook at the bottom. Either show the vertical rebar on the plans or indicate the placement will be in a monopour method. If you wish to leave either option available, please make a note on the plans to allow either option. R403.1.3 6.Where the new addition meets the existing, show that the top plate of the wall will have at least a 24 inch lap splice, or show a strap connecting the old and new plates. R602.3.2 7.On the Section view, indicate that the bottom of the footings are at least 18 inches below grade (for frost depth), and that the poly vapor barrier in the crawl space is black. 8.Please show the landing (deck, patio, steps, etc.) at each of the exterior doors. R311.4.3 9.Show on the plans that the garage slab slopes toward the overhead door openings. 10.Smoke alarms will be required throughout the house in all bedrooms and at hallways serving bedrooms. All smoke alarms shall be hard-wired and interconnected in new areas; and in existing areas where an attic or crawl space exists that would provide access for wiring. Please note this on the plans. R313.2. Page 2 of 2