2010-0381 Winged Pig Tavern.pdf
City of Edmonds
PLAN REVIEW COMMENTS
BUILDING DIVISION
(425) 771-0220
DATE: June 17, 2010
TO: Michael Young
Michael@olivescafewinebar.com
FROM: Leif Bjorback, Assistant Building Official
RE: Plan Check: 2010-0381
Project: The Winged Pig Tavern
th
Project Address: 203 5 Ave S
During review of the plans for the above noted project, it was found that the following information,
clarifications or changes are needed. Please provide written responses as to where the changes can
be found on the plans, and submit revised plans/documents to Theresa Umbaugh, Senior Permit
Coordinator. Thank you.
1.Please note on page CS-1 that the Construction Type is VB, not V. This may be
redlined.
2.IBC Table 508.3.3 requires a 2 hour fire-resistive separation wall between the new A
occupancy and the existing M/B occupancies on either end of the space. Please provide the
approved listing and details for the rated wall assemblies on the plans. If you wish to propose
non-separated uses (to omit the fire rating of the walls) according to IBC 508.3.2, please
provide an accurate floor plan of the entire building showing the total square footage. Non-
separated use buildings containing an A-2 occupancy must be fire sprinklered where the fire
area exceeds 5000 square feet. IBC 903.2.1.2
3.Please show on the plans how the space will be heated and ventilated or indicate on the plans
that Mechanical will be a separate permit. IBC 1203.
4.Indicate that panic hardware will be provide at the north exit door. IBC 1008.1.9
5.Please complete and submit the Interior and Exterior Light Summary forms, attached.