Loading...
2010-0405 Celtic Cowboy plumbing.pdf City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: June 28, 2010 TO: Brian Knopf bknopf@gmail.com FROM: Leif Bjorback, Assistant Building Official RE: Plan Check: 2010-0405 Project: Celtic Cowboy Plumbing th Project Address: 21104 70 Ave W During review of the plans for the above noted project, it was found that the following information, clarifications or changes are needed. Please provide written responses as to where the changes can be found on the plans, and submit revised plans/documents to Theresa Umbaugh, Senior Permit Coordinator. Thank you. This is not a complete review as the plans are not complete. 1.Show sizes and materials for gas piping, and show meter location so that line lengths can be determined. 2.Show pipe sizes for water supply piping. Include line to toilet. Show point of connection. 3.Show pipe sizes and layout for drain waste and vent system. If portions are existing, please call this out. Include grease trap location and associated drains and venting. 4.Backflow prevention devices are required on the dishwasher, and at the ice machine, coffee maker and beverage dispenser where connected directly to the potable water supply. Indicate the appropriate device for each application. 5.Indicate the location and backflow prevention device for premise isolation.