Loading...
2010-0533 Timms addition.pdf City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: August 23, 2010 TO: Natalie Timms Email: natalie63@hotmail.com FROM: Leif Bjorback, Assistant Building Official RE: Plan Check: 2010-0533 Project: Addition th Project Address: 6510 170 Pl SW During review of the plans for the above noted project, it was found that the following information, clarifications or changes are needed. Please provide written responses as to where the changes can be found on the plans, and submit revised plans/documents to a Permit Coordinator. If you choose, the alterations to the plans may be made in person by visiting our office. Thank you. 1.Please have the engineer of record sign the S pages of the plans. 2.The structural calcs state to verify existing exterior walls are sheathed with plywood and nailed with 8d nails @ 6 inches o.c. and edges blocked. Please add this note to the plans. 3.Please clarify the approach to be used for whole house ventilation. a.Since the VIAQ is no longer adopted by the state, please design by, and use references to section M1508 of the IRC. b.Show the location of the furnace on the plans and indicate the type and size of supply fan (per M1508.6) or integrated air intake (M1508.5) to be used. Be aware that neither of these approaches utilizes an exhaust fan in the system. 4.Please show smoke alarms in the existing bedrooms, the hallway serving the bedrooms, and one on the lower floor level. R314.3.