PLAN REVIEW COMMENTS
BUILDING DIVISION
(425) 771-0220
DATE: September 2, 2010
TO: Michael T Schohl
Eagle Gas Mechanical Inc.
office@eagle-gas.com
FROM: Leif Bjorback, Assistant Building Official
RE: Plan Check: 2010-0620
Project: Axis Physical Therapy Gas Piping
th
Project Address: 21009 76 Ave W
During review of the plans for the above noted project, it was found that the following information,
clarifications or changes are needed. Please provide written responses as to where the changes can
be found on the plans, and submit revised plans/documents to Permit Specialist Linda Thornquist.
Thank you.
1.Additional information on the piping plan is necessary to properly review your proposed
work. Please provide lengths and sizes of all branches from the meter to each of the outlets.
It is not possible to properly size each branch without knowing its length.
2.Please clarify what is meant by the term Clean up as used on the plans. What appliances
are served by that line and what are their BTU capacities?
3.It would be very helpful to show a north arrow on the plan for orientation and location
purposes.