2010-0620 Axis Gas Piping.pdf City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: September 2, 2010 TO: Michael T Schohl Eagle Gas Mechanical Inc. office@eagle-gas.com FROM: Leif Bjorback, Assistant Building Official RE: Plan Check: 2010-0620 Project: Axis Physical Therapy Gas Piping th Project Address: 21009 76 Ave W During review of the plans for the above noted project, it was found that the following information, clarifications or changes are needed. Please provide written responses as to where the changes can be found on the plans, and submit revised plans/documents to Permit Specialist Linda Thornquist. Thank you. 1.Additional information on the piping plan is necessary to properly review your proposed work. Please provide lengths and sizes of all branches from the meter to each of the outlets. It is not possible to properly size each branch without knowing its length. 2.Please clarify what is meant by the term “Clean up” as used on the plans. What appliances are served by that line and what are their BTU capacities? 3.It would be very helpful to show a north arrow on the plan for orientation and location purposes.