2010-0654 O'Reilly Auto Parts #3.pdf City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: August 10, 2011 TO: Jessica Iverson Email: jiverson@cmarch.com FROM: Leif Bjorback, Assistant Building Official rd RE: Plan Check: 2010-0654 3 review Project: O’Reilly Auto Parts Project Address: 23005 Highway 99 During review of the plans for the above noted project, it was found that the following information, clarifications or changes are needed. Please provide written responses as to where the changes can be found on the plans, and submit revised plans/documents to a Permit Coordinator. Text in italics indicates a previous review comment. Thank you. 1.Required special inspections have been identified for the project. They will include soils inspections by the geotechnical engineer as well as structural special inspections for concrete, steel and high (strength) bolting. Please fill out, sign and return the attached special inspection agreement forms (one for each agency). As your recent email stated, we are still awaiting the signed special inspection form for soils, as well as the signature on both forms by the general contractor. 2.Response acceptable. 3.Suspended ceilings with areas exceeding 2500 square feet are required to incorporate a seismic separation joint or a a full height wall partition that breaks up the area. Please show on the plans how this will be accomplished. For more information please refer to Field Technical Document 401 as found at the NW Wall and Ceiling Bureau website. www.nwcb.org The revised sheet F1 now has additional details for the ceiling system, but does not include design and detail for a seismic separation joint or a full height wall partition as requested. Please provide this information on the plans.