2010-0924 Dr Kitts mechanical.pdf City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: December 13, 2010 TO: Daimian Bingham Evergreen Refrigeration Email: Daimian@EvergreenHVAC.com FROM: Leif Bjorback, Assistant Building Official RE: Plan Check: 2010-0924 Project: Dr.Kitts Mechanical th Project Address: 201 5 Avenue South #104 During review of the plans for the above noted project, it was found that the following information, clarifications or changes are needed. Please provide written responses as to where the changes can be found on the plans, and submit revised plans/documents to Linda Thornquist, Permit Coordinator. Thank you. 1.Please include on the plans a description of the scope of work. The application originally stated the permit was for 3 exhaust fans only. 2.What function does the BF-1 serve? Please provide adequate information on the plans. 3.The med gas closet is rated as one-hour construction. Penetrations by ductwork must be protected by one-hour-rated shafts to the exterior of the building. Please provide a detail for the location of the penetrations of both the supply and exhaust ducts into the closet. If fire wrap is to be utilized as suggested on the TI plans, provide specs and sufficient details to show code compliance. IFC 3006