PLAN REVIEW COMMENTS
BUILDING DIVISION
(425) 771-0220
DATE: December 28, 2010
TO: Daniel Policiuc
A&D Construction Services
Danielpoliciuc@hotmail.com
FROM: Leif Bjorback, Assistant Building Official
RE: Plan Check: 2010-0949
Project: Retina Eye Care
th
Project Address: 21616 76 Ave W #104
During review of the plans for the above noted project, it was found that the following information,
clarifications or changes are needed. Please provide written responses as to where the changes can
be found on the plans, and submit revised plans/documents to Linda Thornquist, Permit
Coordinator. Thank you.
1.Washington State law requires that permit documents prepared by an architect be stamped
and signed by the architect. It appears that these drawings have been prepared by Connell
Design, and they should be stamped and signed.
2.On the Site Plan, the scope of the note Contract This Area is unclear. The arrow seems to
point to the clouded area which includes a note regarding the addition of new HC parking
signage. If this is not the scope, please remove references to the parking alterations including
the cloud and the accessible sign detail.
3.Alterations to a building, in particular the removal of the accessible restroom, may not
reduce the the accessibility of the building. An exception would be to provide floor plans
showing access from the suite to accessible restrooms within the building to show that the
existing building still complies with the code. IBC 3411.3
4.The alterations require accessibility upgrades per WAC 51.50 (IBC 3411.7). On the plans
clearly show that the entire exterior and interior accessible route of travel complies with
current code, or provide upgrades per the previously referenced section. If you choose to use
exception #1 of that section, provide a letter stamped and signed by the architect (reference
the code exception), stating the overall project cost, 20% of the project cost, and list the
accessibility upgrades that will be done as part of this permit as well as showing that the
total cost of the upgrades is at least 20%.
5.Please provide a detail showing accessible hardware for the sliding doors at rooms 110 and
111, and add a note that all door hardware is to be lever style or otherwise code compliant.
IBC 1008.1.9.1