2011-0242 Woodhaven Vet Clinic.pdf City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: May 9, 2011 TO: Richard Utt Email: rutt@cornerstonearch.com FROM: Leif Bjorback, Assistant Building Official RE: Plan Check: 2011-0242 Project: Woodhaven Veterinary Clinic Project Address: 23204 Edmonds Way During review of the plans for the above noted project, it was found that the following information, clarifications or changes are needed. Please provide written responses as to where the changes can be found on the plans, and submit revised plans/documents to Marie Harrison, Senior Permit Coordinator. This review includes structural and non-structural. Non-structural 1.Please provide energy compliance forms for Energy Metering (available on www.neec.net); and either the Building Envelope form (available on www.neec.net) or the Table 13-1 worksheet from the 2009 WS-NREC. Show on the plans the R values for wall, roof and slab insulation; and the maximum U value(s) for windows. 2.Show clearly on the plans that the med gas closet is enclosed within fire rated construction. Provide details of listed assemblies for walls and roof ceiling construction. Include the ventilation as required by IFC 3006. 3.Show signage details and dimensions for the accessible parking stalls. IBC 1110.1 and ANSI A117.1 section 502.7 4.Provide details for the sidewalk grade and/or curb ramp at the parking access aisle. ANSI A117.1 section 406.3 5.Add dimensions to the reception desk to show compliance with ANSI A117.1 section 904.3. At least a 36 inch portion of the counter must be no more than 36 inches in height. 6.Provide clear floor space of 18 inches on the latch side of door # 128A to provide maneuvering clearance on the pull side. ANSI A117.1 section 404.2.3 7.Please show on the plans how roof ventilation will be achieved. IBC 1203.2 8.Attached are Special Inspection Agreement forms for Soils and for Structural. Please obtain signatures and return both forms prior to issuance of the permit. Structural 9.Roof beam #17 as shown on the plans (W18x40) does not match what is in the calculations (W12x65). Please clarify the size of this beam. Include new calculations if using the W18x40 size. 10.Please provide structural calculations for the seismic connections of the roof top mechanical units as they are each over 400 pounds. Include connections for unit-to-curb as well as curb- to-roof. Mechanical 11. Please revise the Outdoor Air Calculations as shown on sheet M-1.0. They do not seem to agree with IMC Equation 4-1 and Table 403.3. Plumbing 12. Clarify the pipe sizing for the 1½” O2 and the ½” VAC lines shown on sheet P-4.0. Are these dimensions reversed? 13.Please indicate on the plans that the medical gas system will be inspected and verified by a third party agency per UPC 1328. Page 2 of 2