PLAN REVIEW COMMENTS
BUILDING DIVISION
(425) 771-0220
DATE: May 31, 2011
TO: Jereme Wickstrom
Best Plumbing
Fax (206) 633-2202
FROM: Leif Bjorback, Assistant Building Official
RE: Plan Check: 2011-0402
Project: Dicks Drive-in Plumbing
Project Address: 21910 Highway 99
During review of the plans for the above noted project, it was found that the following information,
clarifications or changes are needed. Please provide written responses as to where the changes can
be found on the plans, and submit revised plans/documents to Marie Harrison, Senior Permit
Coordinator.
1.The Sure Seal Floor Drain Trap Sealer is not recognized within the prescriptive requirements
of the UPC. Please provide additional information to justify its use under alternate
materials or indicate the use of trap primers at all floor drains.
2.Please identify the dark blue dashed line that connects the RPBA for Pop with the Filter and
the ice machine (A016) and the coffee maker (A033). It is unclear what this line serves.
3.Please clarify the routing of the soda machine supply lines beyond the RP device.
4.Appliances such as ice machines and coffee makers that are directly connected to potable
water typically must be isolated by RPBA devices, unless they have an integral air gap.
Please provide specifications on these items; otherwise a determination will be made by the
plumbing inspector in the field whether or not backflow protection will be required.
5.The plumbing plans show the following items are connected directly to the sanitary sewer, but
they should be connected to the line flowing to the grease interceptor:
a.The dipper well labeled A026 next to B009 next to index C
b.The floor sinks next to both mobile fryers (labeled B002)
c.The floor drain underneath the four comp prep sink
6.The plumbing plans show all four handsinks as connected to the grease interceptor, but they
should be connected to the line flowing to the sanitary sewer.