2011-0526 Dick's RTU's.pdf
City of Edmonds
PLAN REVIEW COMMENTS
BUILDING DIVISION
(425) 771-0220
DATE: July 19, 2011
TO: Evergreen Refrigeration
Email: Daimiane@EvergreenHVAC.com
FROM: Leif Bjorback, Assistant Building Official
RE: Plan Check: 2011-0526
Project: Dicks Drive-in HVAC
Project Address: 21910 Highway 99
During review of the plans for the above noted project, it was found that the following information,
clarifications or changes are needed. Please provide written responses as to where the changes can
be found on the plans, and submit revised plans/documents to Linda Thornquist, Permit
Coordinator.
1.Gas piping is indicated on the permit application but not on the plans. Either indicate that
gas piping is a separate permit, or provide line drawings and equipment information
sufficient for review.
2.Please provide Outside Air calculations to show compliance with IMC Table 403.3.
3.Please provide stamped and signed calculations and details by a structural engineer for the
RTU seismic attachments as they all exceed 400 lbs. This is to include unit-to-curb and
curb-to-roof attachments.