Loading...
2011-0526 Dick's RTU's.pdf City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: July 19, 2011 TO: Evergreen Refrigeration Email: Daimiane@EvergreenHVAC.com FROM: Leif Bjorback, Assistant Building Official RE: Plan Check: 2011-0526 Project: Dick’s Drive-in HVAC Project Address: 21910 Highway 99 During review of the plans for the above noted project, it was found that the following information, clarifications or changes are needed. Please provide written responses as to where the changes can be found on the plans, and submit revised plans/documents to Linda Thornquist, Permit Coordinator. 1.Gas piping is indicated on the permit application but not on the plans. Either indicate that gas piping is a separate permit, or provide line drawings and equipment information sufficient for review. 2.Please provide Outside Air calculations to show compliance with IMC Table 403.3. 3.Please provide stamped and signed calculations and details by a structural engineer for the RTU seismic attachments as they all exceed 400 lbs. This is to include unit-to-curb and curb-to-roof attachments.