2011-0651 Baicha Tea Room Plumbing.pdf City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: August 23, 2011 TO: Nair’s Plumbing Email: Nairsplumbing@yahoo.com FROM: Leif Bjorback, Assistant Building Official RE: Plan Check: 2011-0651 Project: Baicha Tea Room Plumbing Project Address: 622 5th Ave S During review of the plans for the above noted project, it was found that the following information, clarifications or changes are needed. Please provide written responses as to where the changes can be found on the plans, and submit revised plans/documents to Linda Thornquist, Permit Coordinator. 1.Please indicate on the plans where backflow devices are needed. a.Premise isolation is required by Public Works Water department. The RPBA is to be located inside the building prior to any connections. b.It appears that backflow protection is needed at the commercial dishwasher and the ice maker. Please indicate RPBA devices at each of these fixtures. 2.Show an expansion tank at the water heater. 3.Show the floor drains on the plumbing line drawings. Note that they will need trap primers. 4.Indicate on the plans that indirect drains will be provided for the ice maker, dishwasher and food prep sinks.