2011-0671 Holy Rosary Mechanical #2.pdf City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: September 23, 2011 TO: Steven Knobbs GB Systems Email: Stevenk@gbs-hvac.com FROM: Leif Bjorback, Assistant Building Official nd RE: Plan Check: 2011-0671 2 review Project: Holy Rosary Project Address: 760 Aloha St. During review of the plans for the above noted project, it was found that the following information, clarifications or changes are needed. Please provide written responses as to where the changes can be found on the plans, and submit revised plans/documents to Marie Harrison, Senior Permit Coordinator. 1.Previous item 5. Please provide outside air calculations for the air handler as required by 2009 IMC 403. Indicate whether the calculations are based on IMC Equation 4-1 and Table 403.3 or ASHRAE Standard 62.1. It appears that the proposed 1715 cfm is grossly insufficient to meet the code minimums. Your response indicated that your calculations are based on IMC Table 403.3, but actual calculations were not provided as requested. Again, it appears that the proposed 1715 cfm is grossly insufficient to meet the code minimums, as my very rough calculations using Equation 4-1 indicate that the required cfm well exceeds 10,000 for the building. Please submit outdoor air calculations to show compliance with IMC 403.