2011-0742 Subway.pdf City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: September 21, 2011 TO: Sue Shangguan Woodman Construction Email: Sue@woodmanconstruction.com FROM: Leif Bjorback, Assistant Building Official RE: Plan Check: 2011-0742 Project: Subway Project Address: 10016 Edmonds Way During review of the plans for the above noted project, it was found that the following information, clarifications or changes are needed. Please provide written responses as to where the changes can be found on the plans, and submit revised plans/documents to Marie Harrison, Senior Permit Coordinator. Thank you. 1.Please submit a completed Interior Lighting Summary form which may be found at www.neec.net/energy-codes. 2.Provide a copy of the plan review letter from the Snohomish Health District for your project. 3.On the Title sheet, please make the following changes in the Applicable Codes section: a.The Accessible and Usable Buildings and Facilities should be the 2003 edition, not 2006. b.Delete the reference to the VIAQ, as it is no longer adopted by the state. 4.Please distinguish between existing and new walls on the floor plan. 5.Show a maximum height of 36 inches and a minimum length of 36 inches for the accessible checkout counter. ANSI A117.1 section 904.3 6.The 48 inch tall door into the counter area is noted as self closing. Please note whether or not the door has a latch as well. If so, then provide a clear floor space on the push side of the door 12 inches beyond the latch edge of the door by 48 inches deep. ANSI A117.1 section 404.2.3