2011-1086 GRE HVAC #2.pdf City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: February 2, 2012 TO: Gasline Mechanical Inc. Woodinville, WA 98072 Email: janderson@gaslinemechanical.com FROM: Leif Bjorback, Assistant Building Official nd RE: Plan Check: 2011-1086, 2 review Project: GRE HVAC Project Address: 23020 Edmonds Way During review of the plans for the above noted project, it was found that the following information, clarifications or changes are needed. Please provide written responses as to where the changes can be found on the plans, and submit revised plans/documents to a permit coordinator. Thank you. 1.The floor plans for the common area (Fitness, Media, etc) on the ground floor do not match the approved building plans. Please verify the layout on this set is accurate, otherwise adjust as needed. This item has not been addressed in writing. Please verify the proper floor plan. 2.Completed. 3.Completed. 4.Completed. 5.Completed. 6.The exhaust ducts from the Fitness Room and Restrooms penetrate a 3 hour fire wall into the garage. Show 3 hour fire dampers at these locations. IBC 716.5.1 and IBC Table 716.3.2.1 The SFD’s added at the restroom exhaust are satisfactory, however there is none shown for the Fitness room as requested. 7.A fire rated shaft is required where the supply duct from RTU-1 penetrates the roof and 2 floors. Provide details for construction of the shaft, including the listing of the rated assembly. IBC 708.2 This item has not been addressed, but must be prior to proceeding. Please consult the building designer, and provide a note on the mechanical plans referencing the rated shaft. 8.Please provide stamped and signed calculations and details by a licensed engineer for the RTU seismic attachments as it exceed 400 lbs. This is to include unit-to-curb and curb-to- roof attachments. This item has not been addressed.