20111201121818823.pdfEagle Consulting Engineers, P.S.
PO BOX 523
Olalla WA 98359
hoytjeter@centurytel.net206 356-7790i
Fax
0. 316-2287
To: Burns Fire Systems
PO Box 1110
Granite Falls, WA 98252
Re: Woodhaven Veterinary Clinic
23204 Edmonds Way
Edmonds, WA 98026
Plan Review Number # 20110956
Thursday, December 01, 2011
EECE EDMI 1-08
The above referenced project is in the process of plan review for compliance with
Edmonds ordinances and applicable codes (Fire Suppression only). The following
comments, deficiencies/corrections must be addressed prior to completion of plans review
and subsequent issuance of permits.
Provide revised plans and calculations along with a written response to each of the items
listed below to facilitate a shorter back -check time.
SCOPE OF REVIEW
The scope of this review is for .Hre Suppression requirements of this project.
All features were checked only to the extent allowed by the submittals provided. All
portions of this project are assumed to meet or will meet other departmental requirements,
conditions and concerns before permit approval.
Page 2 of 2
EECE# EDM11-08
Woodhaven Veterinary Clinic 20110956
FIRE SUPPRESSION COMMENTS
Sheet 1
1. It appears that the supply riser is on the exterior of the building. If so, how will it be
heated to prevent freezing? NFPA 8.16.4.1.3
2. Provide a legend for the sprinkler heads. NFPA 13, 22.1.3
Sheet 2
3. The underground line is shown entering the building at a different location than the
riser. Please correct and provide the actual length of the underground pipe. NFPA 13,
22.1.3
Additional corrections may be required following receipt of corrections and additional
information as requested.
Your plans are being reviewed concurrently with the Building Department, Fire
Department, Zoning Department and Public Works Engineering. Changes, clarifications
or additional corrections may be required subsequent to the Building Department plan
review when comments are received from the other concerned departments.
Should you have any inquiries regarding this letter, please contact Hoyt Jeter at (206) 356-
7790 between 8:00 a.m. and 5:00 p.m.
Hoyt Jeter PE