20120215101823536.pdfAjngaoMedical Services, Inc. Everett, ww98201 (425),41-880rfax (4zo)968'4020 Viedical Gas Line Verificatioii Report I Date: 24January 2O12 Job Number: 201742 Contractor: PSF Mechanical Dake/s\/Tinne(n)ofTesting: 23January 2012/072Ohns Facility: Swedish- Edmonds Medical Center 21001 7O"'Avenue West Edmonds, VVA98O20 Scope of Work: Added new Oxygen and Vacuum isolation valves in ceiling above control room in MRI room, also added lea. Oxygen and vacuum outlets. Our firm certifies that the verifier named in the report is properly trained and certified to perform the activities required. All test and measurement equipment is properly calibrated and maintained. As a representative nfAirgas Medical Son/ioeo NW the verifier named in this report has conducted testing and verification of Medical Gas piping systems and related equipment to certify the fn||ovvinQ on the above date. General Findings: A. Medical Gases and Vacuum are incompliance with NFPA99U9Q9ed\: Level B. No crossed lines were found in Medical Gases in tested areas on the day of testing. C. Medical Gases meet minimum concentration. U. Medical Gases meet minimum flow and normal pressure. E. Medical Vacuum meets minimum flow and isotnormal vacuum pressure. F. Most medical Gas System components in area tested are in compliance with NFPA 99(1999ed): See (Note), (Comments), (Recommended Corrections) and (Corrections) G.Medical Gas line purity: PASS #LH01Y10QA(AG) H. 15O#for 24hour Line Pressure Test: PASS City ofEdmonds, Permit #:11'OQ30 1. Attachments: Purity Sheet. Note: Existing Equipmentand Systems NFFY\9g/Y0QQedl#4'Y.4—Anexisting system that b/not /nstrict compliancewith the provisions of this standard shall be permitted to be continued in use as long as the authority having jurisdiction has determined that such use does no/ constitute a distinct hazard tolife. 01-AG.VR-Medicm|Gas Line (1S08ad)'Rev11 PQ 1 of 3 Airgas Medical Services, Inc. Everett, WA 98201 (425)741-8807 fax (425)968-4620 http://www.airgas.com II. Medical Gases: A. Oxygen: 1. Static Line Pressure: 59 psig. 2. Dynamic Outlet Free Flow: >3.5 scfm. 3. Oxygen Concentration: >99.0% 4. Delta Flow: PASS III. Vacuum: A. Medical / Surgical Vacuum: 1. Static Line Vacuum: 23"HgV. 2. Dynamic Outlet Free Flow: >3.0 scfm. 3. Delta Flow: PASS IV. Particulate Line Test: PASS V. Outlets / Inlets Brand: Chemetron A. Quick Connect Style: Chemetron VI. Zone Valves: Chemetron- NCG A. Without down line gauges. VII. Alarms: None • :[•TA►[�7►L� IX. Brazier: Terry D, Barnes A. Brazier Number: MG01- BARNETD894BM B. Plumbing Contractor: PSF Mechanical X. Witness: Tom Goodson- Facilities XI. Comments: A. No Vacuum zone valve. ( existing) B. No down line gauge on oxygen zone valve. ( existing) C. Oxygen line pressure is 59psig. XII. Recommended Corrections: A. Add Vacuum zone valve. B. Add oxygen zone valve with down line gauge. C. Lower oxygen line pressure to 55psig. XIII. Corrections: A. None 01-AG.VR-Medical Gas Line (1999ed)-Rev1.1 Pg 2 of 3 i Airgas Medical Services, Inc. Everett, WA 98201 (425)741-8807 fax (425)968-4620 http://www.airgas.com Tested By: Eric Burt Eric N. Burt, ASSE 6020 Inspector Airgas Medical Services, Inc. eric.burt(cDairgas.com Cell 425-754-1097 Signature Block 01-AG.VR-Medical Gas Line (1999ed)-Rev1.1 Pg 3 of 3