2012-0688 Las Brisas Fireplace.pdf
City of Edmonds
PLAN REVIEW COMMENTS
BUILDING DIVISION
(425) 771-0220
DATE: August 21, 2012
TO: Villas Construction
Email: villasconstruction@gmail.com
FROM: Leif Bjorback, Assistant Building Official
RE: Plan Check: 2012-0688
Project: Las Brisas Fireplace
th
Project Address: 201 5 Ave S Suite 101
During review of the plans for the above noted project, it was found that the following information,
clarifications or changes are needed. Please provide written responses as to where the changes can
be found on the plans, and submit revised plans/documents to a permit coordinator in the
Development Services Department. Thank you.
1.The gas burner appliance must be listed and labeled by an approved agency such as ANSI or
CSA for the use of the appliance. Please provide the listing and associated specifications for
review. An alternate to this would be to provide a design that is stamped and signed by a
Washington State licensed mechanical engineer. IFGC 301.4
2.Provide the listing and specifications for the exhaust fan and hood. Include the listing
agency, CFMs, and installation instructions. Show which exterior wall the duct terminates
through (west or south?) IFGC 304.1