Loading...
2012-0858 Olson SFR2.pdf City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: June 11, 2013 TO: James Thomas jthomas@arch-design.net FROM: Chuck Miller, Plans Examiner RE: Plan Check: 2012-0858 Project: Olson SFR th Project Address: 15500 75 Place W During a review of the plans for the above noted project, it was found that the following information, clarifications or changes are needed. Please provide written responses as to where the changes can be found on the plans, cloud all changes on the revised plans, and submit the revised plans/documents to a Permit Coordinator. Previous items that recur on this list appear in italics. Thank you. On page A3.0: 1.Indicate on the plans the required (2)2x12 DF #2 to be used as driveway deck joists per the revised structural calculations submitted in response to the plan review comments dated November 14, 2012. 2.Foundation – Provide installation criteria for the 2-inch diameter pipe piles/pile caps to be used to support the deck on the west side of the structure – gridlines A-D/5 and detail ‘12/S1.0’. None could be found among the submitted construction documents. 3.Foundation Plan – Eliminate the callout and leader line for an auger cast pile located between piles #7 and #8 – gridlines D.55/3.1 – to avoid confusion and guide proper construction and inspection. 4.Wall Legend – Clarify the detail referenced on page S1.0 for the required construction of the auger cast piles. Detail ‘3/S1.0’ does not appear to apply. 5.Wall Legend - Clarify the difference between the grade beam reinforcement noted and that required in detail ‘1/S1.0’ and on pages 1 and 2 of the provided structural calculations. On page A3.3 – (this page appears to be missing from the resubmittal documents): 6.Clarify the difference between the length and type of shear walls shown on gridline ‘C/F’ and that represented on page ‘A4’ of the provided structural calculations. 7.Clarify the omission on the ‘P1-4’ shear wall along gridline ‘2’ represented on page ‘A4’ of the provided structural calculations. 8.Indicate the required construction to complete the shear transfer from the roof diaphragm to the ‘P1-4’ shear wall along gridline ‘2’. 9.Clarify the callout for ‘Beam 4’ – #2 Hem-fir 6x8 – the point load from the girder truss does not appear to have been accounted for. 10.Clarify the callout for ‘Beam 8’ – #2 Hem-fir 4x4 – the point load from the 2x12 ridge beam does not appear to have been accounted for. On page S1.0: 11.Provide legible structural details to guide proper construction and inspection in the field. After being reduced and copied, the provided details are difficult to read, even in a well-lit office environment. The details are exactly as submitted earlier. There appears to be room on page S1.1 that would allow a few to be moved there and for all of the details to be enlarged. The detail references on the preceding pages would need to be changed also. 12.Clarify detail #16 – it appears to be identical to detail #15 and different than that of the same number in the provided structural calculations. Detail ‘16’ on page S1.0 is exactly like detail ‘15/S1.0’ and represents a condition where the joists are perpendicular to the shear wall below. The reference made to detail ‘16/S1.0’ on page A3.2 is where the floor joists are parallel to the shear wall below. Detail ‘16’ in the provided 8-1/2”x11” structural calculations properly indicates the construction requirements where the joists are parallel to the shear wall below. These plan review comments summarize the Building Division concerns regarding the construction documents that have been submitted to date. Reviews by other divisions, such as Planning, Engineering, or Fire, may result in additional review comments. Please include the response(s) to the attached peer review dated June 7, 2013, completed by Landau Associates, with any other documents brought in to the Permit Center at the time of resubmittal. Page 2 of 2