2012-1122 Aldercrest Addition #2.pdf City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: February 1, 2013 TO: Coates Design Architects Email: Bob@coatesdesign.com FROM: Leif Bjorback, Assistant Building Official nd RE: Plan Check: 2012-1122, 2 review Project: Aldercrest Health and Rehab. nd Project Address: 21400 72 Ave W During review of the plans for the above noted project, it was found that the following information, clarifications or changes are needed. Please provide written responses as to where the changes can be found on the plans, and submit revised plans/documents to a permit coordinator in the Development Services Department. Thank you. Note that previous comments appear in italics. 1.Previous item 3: The new exterior west wall of Room 104 is situated 16 feet from the east exterior wall of the existing west wing of the building. It appears on the original construction drawings that these are separate buildings on the same lot. In the new configuration, an imaginary lot line will need to be established for the purpose of determining fire separation distance and allowable openings in the exterior walls. Please show this imaginary lot line on the plans, and show how the respective exterior wall openings of both buildings comply with IBC 705.8. See also IBC 705.3. The limitation of openings in exterior walls applies to the existing bedroom walls facing the new addition as well as to the new walls that you have addressed. Please demonstrate how these existing bedroom walls comply with this code section. Also related to this issue, provide revised plans addressing the 1/22/13 DOH review comment #3 stating “each resident bedroom must have an exterior window located twenty-four feet or more from another building or the opposite wall of a court.” 2.Previous item 12: Special inspections have been identified for the project. Please complete and return the attached special inspection agreement forms. These forms must be completed and approved prior to issuance of the permit. We have not received the special inspection forms as your response letter indicates. Please provide the signed forms prior to issuance of the permit.