PLAN REVIEW COMMENTS
BUILDING DIVISION
(425) 771-0220
DATE: July 30, 2013
TO: Jonathan Richards
jonathan_59@hotmail.com
FROM: Chuck Miller, Plans Examiner
RE: Plan Check: BLD2013-0191
Project: Ching/Chang garage
Project Address: 17134 Talbot Road
During a review of the plans for the above noted project, it was found that the following information,
clarifications or changes are needed. Please provide written responses as to where the changes can be
found on the plans, cloud all changes on the revised plans, and submit the revised plans/documents to a
Permit Coordinator. Previous items that recur on this list appear in italics. Thank you.
On page A6.0:
1.Roof Plan - Clarify the callout for the 5-1/8x10-1/2 GLB to be used to support the roof trusses.
Using the typical roof truss layout for a hip roof, a hip-master located 8 feet from the building
corner will result in a point load over the beam. Under this condition, the beam appears to be
over spanned and deflects beyond that allowed per Table R301.7. Provide beam calculations
supporting the designated member with loads reflecting the actual construction/truss orientation.
If a GLB, provide the design, species, and lay-up in the response. Resubmittal response dated 7-
19-2013 The hand-written depiction of the loads supported by Beam H1 5-1/8x10 24F-V4
GLB are different than that entered in the ConstructionCalc wood beam calculator. It appears
that the live and dead loads for the Partial Load D section have been entered as the live loads
for each of the partially loaded sections, and the live and dead loads for the Partial Load E
section have been entered as the dead loads for each of the partially loaded sections. While the
result is a greater than actual load on the Partial Load D section (0-4 feet), the far lower than
actual load on the Partial Load E section (4-16 feet) results in an over spanned beam being
approved. Also, the unconventional girder truss placement results in a larger Partial Load E
section and a larger beam to support the load.