2013-0240 Waite carport conversion-garage addition.pdf
City of Edmonds
PLAN REVIEW COMMENTS
BUILDING DIVISION
(425) 771-0220
DATE: March 26, 2013
TO: J. K. Yamane
jkyamane@comcast.net
FROM: Chuck Miller, Plans Examiner
RE: Plan Check: BLD2013-0240
Project: Waite carport conversion-garage addition
nd
Project Address: 1154 2 Avenue S
During a review of the plans for the above noted project, it was found that the following information,
clarifications or changes are needed. Please provide written responses as to where the changes can be
found on the plans, cloud all changes on the revised plans, and submit the revised plans/documents to a
Permit Coordinator. Thank you.
On page A-1:
1.General Note Indicate on the plans any openings in the west wall of the house into the
carport/garage. No windows (in the wall or doors) or ventilation intake and exhaust openings are
allowed. The door must meet the requirements of R302.5.1.
2.General Note Indicate on the plans the required dwelling/garage separation per Table R302.6.
3.Wall Section AA/A-1 Indicate on the plans the roof sheathing material to be used for the 6 foot
and 10 foot additions to each end of the existing carport roof.
4.Wall Section AA/A-1 Indicate on the plans the required attachment of the roof sheathing per
R602.3(1).
5.Wall Section AA/A-1 Clarify the callout for the 2x10 DF #2/btr rafters at 16 on-center. The
deflection of the overhang is beyond that allowed per Table R301.7.
6.Wall Section AA/A-1 Indicate on the plans the required attachment of the top plate of the in-
fill wall to the existing framing per R602.3(1).
7.Wall Section AA/A-1 Indicate on the plans the required frost protection of the footing per
R403.1.4.1.
8.Wall Section AA/A-1 Indicate on the plans the required reinforcement of the slab-on-ground
with turned-down footing per R403.1.3.2. Note the requirement for slabs-on-ground cast
monolithically with the footing.
9.Existing and Proposed Roof Plan Clarify the difference between the roof overhang indicated
for the west eave and that represented in the North Elevation.
10.Existing and Proposed Roof Plan Indicate on the plans the means to be used to support the east
end of the roof rafters at the 6 foot addition.
Page 2 of 2