2013-0264 Rice remodel-addition.pdf
City of Edmonds
PLAN REVIEW COMMENTS
BUILDING DIVISION
(425) 771-0220
DATE: April 30, 2013
TO: Kristin Hanson
hansondesign@hotmail.com
FROM: Chuck Miller, Plans Examiner
RE: Plan Check: BLD2013-0264
Project: Rice remodel-addition
Project Address: 624 Alder Street
During a review of the plans for the above noted project, it was found that the following information,
clarifications or changes are needed. Please provide written responses as to where the changes can be
found on the plans, cloud all changes on the revised plans, and submit the revised plans/documents to a
Permit Coordinator. Thank you.
On pages 5 and S-2:
1.Indicate on the plans a callout for hold-downs TD-3 at each end of the shear wall along gridline
2 as required per pages 23 & 24 of the provided structural calculations.
On pages 6 and S-2:
2.Provide a detail and a reference to it on the plans for the means to be used to meet the
requirements of Table R302.1. The one-foot overhang along the east side of the structure
extends 6-inches into the minimum fire separation distance, requiring 1-hour fire resistance rated
construction on the underside of the eaves. The fire resistance rating can be reduced to 0-hours
if fire blocking (solid-unvented) is installed from the wall top plate to the underside of the roof
sheathing and if no gable vents are installed. As long as the roof ventilation requirements of
R806 are met by the remaining openings provided, no additional measures are necessary.