2013-0573 Trost deck .pdf City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: June 4, 2013 TO: Douglas Trost dougtrost@hotmail.com FROM: Chuck Miller, Plans Examiner RE: Plan Check: BLD2013-0573 Project: Trost deck th Project Address: 7731 194 Street SW During a review of the plans for the above noted project, it was found that the following information, clarifications or changes are needed. Please provide written responses as to where the changes can be found on the plans, cloud all changes on the revised plans, and submit the revised plans/documents to a Permit Coordinator. Thank you. On page 1: 1.Indicate on the plans the required landing at the sliding door per R311.3. At a minimum, the landing needs to be as wide as the operable portion of the door and 36 inches deep in the direction of travel. It needs to be within 7-3/4” of the top of the door threshold. On page 2: 2.Indicate on the plans the distance between the posts supporting, or the span of the 4x6 beams. Include the amount of overhang, or cantilever, where applicable. 3.Indicate on the plans the distance between the 4x6 beams or span of the 2x6 joists. Include the amount of overhang, or cantilever, where applicable. 4.Clarify the callout for the 3/8x5 wedge anchors placed 24” on-center for the attachment of the ledger – they do not appear to meet the loading conditions represented on the plans. Estimating a six foot distance from the first beam line to the ledger (see plan review note #3), an approximate 150 pound-per-lineal-foot (PLF) load would need a minimum 1/2 –inch bolt, embedded 6-inches in concrete, placed at 24’’ on-center, to support the load per the National Design Specification for Wood Construction (NDS).