2013-0904 Lewis Addition.pdf City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: September 23, 2013 TO: Jay Lewis Email: jaylewis32@gmail.com FROM: Leif Bjorback, Building Official RE: Plan Check: 2013-0904 Project: Lewis Residence Addition th Project Address: 1126 8 Ave S During review of the plans for the above noted project, it was found that the following information, clarifications or changes are needed. Please provide written responses as to where the changes can be found on the plans, and submit revised plans/documents to a permit coordinator in the Development Services Department. Thank you. 1.Structural plan sheets S2.1 and S2.2 need to be signed by the appropriate design professional. 2.Exhaust fans with a minimum of 50 cfm are required in each of the bathrooms and toilet room. If you wish, this is an item that I can redline on the plan. 3.Please identify on the plan the girder over the gym that carries the cantilevered deck joists. In the structural calculations it appears this may be the “Beam Supporting Deck Framing.” Please show the distance of the backspan on the plan. The calcs show a backspan of 8 feet but on the plan this scales to approximately 4.5 feet. 4.Please provide structural calculations for the 3-1/8”x9” glulam and the 2x8 joists at the entry. 5.Specify on the plans the size and type of anchor bolts for the HTT4’s and HTT5’s.