2013-0922 Winterer patio cover3.pdf
City of Edmonds
PLAN REVIEW COMMENTS
BUILDING DIVISION
(425) 771-0220
DATE: March 25, 2014
TO: Ryan Peck
ryan@rapeckdesign.com
FROM: Chuck Miller, Plans Examiner
RE: Plan Check: BLD2013-0922
Project: Winterer patio cover
th
Project Address: 9230 215 Street SW
During a review of the plans by the Building Division for the above noted project, it was found that
the following information, clarifications, or changes are needed. A complete review cannot be
performed until the revised plans/documents, including a written response indicating where the
clouded or otherwise highlighted changes can be found on the revised plans, have been submitted
to a Permit Coordinator. Reviews by other divisions, such as Planning, Engineering, or Fire, may
result in additional comments. Items that recur on this list appear in italics.
On sheet A1.1
1.Typical Detail - Provide specifications on the corrugated roof material to be used as a
roof covering and the means of attachment required to resist the component and cladding
loads (wind/uplift) specified in Table R301.2(2). The resubmitted information provided in
response to the prior review comments does not appear to include any of the manufacturers
installation requirements for use as a patio cover see attached. The requirements for
installation (purlins, corrugated horizontal closure strips, fasteners, etc.) should be noted on
the construction documents or referenced and attached to guide proper installation and
inspection.
2.Typical Detail Indicate on the plans the required construction to resist lateral loads per
R301.1. There is no prescriptive path for the use of the corrugated roofing as a means of
providing lateral resistance and must therefore be supported by information from the
manufacturer. Alternatively, knee bracing may be an acceptable option see attached.
3.Structural Plan - Clarify the callout for the 12 on-center 2x6 Hem-Fir #2 rafters used to
support the corrugated roofing. The overhang deflects beyond that allowed per Table
R301.7 and would fail when subjected to the design snow load. The overhang did not
appear to be accounted for in the provided structural calculations.
4.Structural Plan - Clarify the callout for the 4x12 Hem-Fir #2 beams used to support the roof
rafters. The overhang deflects beyond that allowed per Table R301.7 and would fail when
subjected to the design snow load. The overhang did not appear to be accounted for in the
provided structural calculations.