2013-0931 Dedonker SFR2.pdf
City of Edmonds
PLAN REVIEW COMMENTS
BUILDING DIVISION
(425) 771-0220
DATE: October 24, 2013
TO: Michael & Candace Dedonker
mikebdz@gmail.com
FROM: Chuck Miller, Plans Examiner
RE: Plan Check: BLD2013-0931
Project: Dedonker SFR
nd
Project Address: 411 2Avenue N
During a review of the plans by the Building Division for the above noted project, it was found that
the following information, clarifications, or changes are needed. A complete review cannot be
performed until the revised plans/documents, including a written response indicating where the
clouded changes can be found on the plans, have been submitted to a Permit Coordinator.
Reviews by other divisions, such as Planning, Engineering, or Fire, may result in additional
comments. Items that recur on this list appear in italics.
On page A0.3:
1.Attached Table 406.2 Energy Credits (Debits) - Indicate on the plans the required energy
credits to be selected per WSEC R406. No information was provided in response to the
prior plan review comment.
2.Provide a completed Simple Heating System Size worksheet (see attached) or other
documentation used to determine the maximum heat output of the furnace. No information
was provided in response to the prior plan review comment.
On page A2.1:
3.Floor Plan Indicate on the plans the required safety glazing per R308.4.5 for the north-
most 3.0x5.0 and 3.0x2.0 windows in the west wall of the Master Bath. No information
was provided in response to the prior plan review comment.
4.Floor Plan Indicate on the plans the required safety glazing per R308.4.2 for the 3.0x5.0
window adjacent the door in the west wall of the Laundry/Mud Room. No information was
provided in response to the prior plan review comment.