PLAN REVIEW COMMENTS
BUILDING DIVISION
(425) 771-0220
DATE: October 16, 2013
TO: Robert Purser
Rob.purser@gmail.com
FROM: Chuck Miller, Plans Examiner
RE: Plan Check: BLD2013-1018
Project: Purser SFR
Project Address: 922 Cedar Street
During a review of the plans by the Building Division for the above noted project, it was found that
the following information, clarifications, or changes are needed. A complete review cannot be
performed until the revised plans/documents, including a written response indicating where the
clouded changes can be found on the plans, have been submitted to a Permit Coordinator.
Reviews by other divisions, such as Planning, Engineering, or Fire, may result in additional
comments.
On page A3:
1.Foundation Plan - Provide a callout for detail 2 on page G1 for the continuous
footings/foundations to guide proper construction and inspection.
2.Foundation Plan Clarify the callout for the STHD14 holdowns to be used at the ends of
the P1-2 braced wall panels on each side of the garage door opening. The location of the
holdowns in the concrete stem wall as indicated in detail 1 on page L1 places them in an
endwall condition, resulting in a stated manufacturer capacity lower than that required in
the provided structural calculations.