Loading...
2014-0238 Swedish ED - M&P (Rainbow)#2.pdf June 22, 2014 Mr. Leif Bjorback Building Official City of Edmonds 121Fifth Avenue North Edmonds, Washington98020-3145 Subject:Swedish Edmonds Ambulatory Care Center MechanicalPermitReview02–2014-0238 Ihave received and reviewed the above referenced project for conformance with the following codes, as adopted and amended by the State of Washington and the City of Edmonds: 2012International Mechanical Code (IMC) 2012International Fuel Gas Code (IFGC) 2012 Uniform Plumbing Code (UPC) 2012Washington State Energy Code, WAC 51-11 (WSEC) The comments listed below only apply to the documents submitted with the building permitapplication for the mechanical, plumbing and medical gas reviews: 1.A written response is required to the first review, including medical gas review. 2.The Washington State Energy Code Compliance Forms should be revised and resubmitted; theforms make multiple references to a sheet M300 which is not in the plans; items are marked as not applicable but then there is a sheet reference.Thisitem is carried over from the first review. 3.Sheet M2.00A: More comprehensive pipe size callouts are required on the plan. 4.Sheet M2.00B: Plan indicates an existing acid resistant waste(ARW)line connecting to a new sanitary waste line not labeled as ARW. Provide explanation or modify plans as required. 5.Indicate location of natural gas underground containment vent locations on plan andprovide installation detail per IFGC requirements. 6.Sheet M2.01A: More comprehensive pipe size callouts are required on the plan. For example the 4”CW line that runs south from the mechanical room th Rainbow Consulting Mechanical Engineering336 NW 50Street, Seattle, WA 98107www.rainbowconsulting-me.com Steven Rainbow, PEPhone 206.235.6002steven@rainbowconsulting-me.com Swedish Edmonds Ambulatory Care Center Mechanical Review02 June 22,2014 Page 2of 2 and then tees after grid line 3 has no size callouts after the tee. It is alsohard to see how this matches the domestic water riser diagram on sheet M7.04. 7.Fan Coil Units: The designof thefan coil unit ducting does not appear to be complete –typical for all. If these fan coil units are not provided with economizers, then the exception taken and compliance should be noted on the plans. 8.Sheet M4.03: The plume exhaust fan appears to be locatedon top of a roof drain –review location. 9.Sheet M4.03: Provide fireplace vent termination installation detail. 10.Sheet M4.03: The water line feeding the fountain downstream of the backflow preventer should be labeled as non-potable. 11.Sheet M7.05: Riser indicates that the condensate drain from the AHU is hard- piped to the sanitary waste line; this should be changed to an indirect waste. If you have any questions or require additional clarification on any of the items contained in this letter, please email me at steven@rainbowconsulting-me.com or contact me directly at 206-235-6002. Sincerely, Rainbow Consulting Steven Rainbow, PE cc:Douglas Beck, Beck & Associates, PLLC, beckpllc@msn.com th Rainbow Consulting Mechanical Engineering336 NW 50Street, Seattle, WA 98107www.rainbowconsulting-me.com Steven Rainbow, PEPhone 206.235.6002steven@rainbowconsulting-me.com