May 19,Z024
To: John VVestf U
City ofEdmonds — Office o/Fire Marshal
121 5= Avenue North
Edmonds, VVA98020
Re: Sherwin Williams (Westgate 22OU4100yAvenue West)
Permit No.: BLD20140357
Correction Notice #1 (Fire K4amha|)
JPCProject Nu.: 14'0374
John:
Please see the attached drawing revisions for the Sherwin Williams project at Westgate Center. All
changes and additions have been bubbled on the indicated revised drawing sheets.
1. Sheet 1-0.0: Deferred submittals — omit Fire Alarm System and Re Sprinkler System unless
voluntary systems aedesired.
Respor'se:T'heurmms11meMarrn" and °Ii1pe [mve 1)eem msnmoved from* our deferred
submmhtM |st omyheel k0.0.
2. Sheet |'O.0:Note "Intent is tomaintain tenant space aomercantile occupancy group within limits
of single non-sprinklered control area for flammable and combustible liquid storage. Inventory of
Class 113, IC, 11, and IIIA will vary day to day, never in excess of 1,600 gallons limit for non-sprinklered
space per Z012IFC table 57O43.4.1.:nrother approved wording.
Res�pomse:,rheatatennentabove leem4muluded omsheet i-0.0.
3. Submit letter with application from Robert Sommers, Senior Project Engineer for Sherwin Williams,
dated February 7,2O14,attached inthis email.
4. Sheet 1'3.1: Label space with exterior access at Northwest corner ofproject.
Reapomse�'Ihkpmomn[imskw(,flmU�)e|ecJ"IlNectrkm�and RoM Acc�ess(0mDdh,,ig Commmom)",
S. Sheet 1-3.1: Provide minimum rated 2A:20B:C portable One extinguisher (typical) for ordinary
(moderaie)Class 8hazard.
Respcx'ise� Refer to rev�se(J Keynote M/11-3,1.
Please contact us regarding any questions or concerns you may have.
Sincerely,
Amy Colby
]PCArdhitects
(425)641'92OOExt. 329
1125 641 9200 1 «911»6Ave wc Suite 206 ael|°me'mmpomw 1 wwwJpcarc .teuccom
To: Annv Colby ; Carrie Walker
Scott Thompson
From: John VVeatfaU'Fire Marshal 425.771.O213
Subject: BLD 2014-0367 SHERWIN-WILLIAMS WESTGATE
The Fire Department provides the following comments and corrections in accordance with the 2012
International Fire Code and Edmonds Community Development Code Title 19 for existing 4810 s.f.
Mercantile group compartment.
1. Sheet 1-0.0 Deferred submittals omit FIRE ALARM SYSTEM and FIRE SPRINKLER
SYSTEM unless voluntary systems are desired.
2. Sheet 1-0.0 Note: "INTENT |8T[>MAINTAIN TENANT SPACE /\SMERCANTILE
OCCUPANCY GROUP WITHIN LIMITS OFSINGLE N(}N8PR|NKLEREQCONTROL AREA
FOR FLAMMABLE AND COMBUSTIBLE LIQUID STORAGE. INVENTORY [)FCLASS IB, IC, ||'
AND IIIA WILL VARY DAY TODAY, NEVER |NEXCESS DF1.O0OGALLONS LIMIT FOR
NDN8PF||NKLERED SPACE PER 2012 IFC TABLE 5704.3.4.1." orother approved wording.
3. Submit letter with application from Robert Sonnnnera, Senior Project Engineer for Sherwin
Williams, dated February 7.2O14,attached inthis email.
4. Sheet 1-3.1 Label space with exterior access @NVVcorner ufproject.
5. Sheet 1'3.1 Provide minimum rated 2A:20B:C portable fire extinguisher (tvpioa|)for
ordinary (moderate) C|eaa B hazard.