PLAN REVIEW
- BUILDING DIVISION
(425) 771-0220
DATE: May 15, 2014
TO: Stuart McFeely
FROM: Chuck Miller, Plans Examiner
RE: Plan Check: BLD2014-0384
Project: Scheafer addition
Project Address: 21432 86"' Avenue W
During a review of the plans by the Building Division for the above noted project, it was found that
the following information, clarifications, or changes are needed. A complete review cannot be
performed until the revised plans/documents, including a written response indicating where the
`clouded' or otherwise highlighted changes can be found on the revised plans, have been submitted
to a Permit Coordinator. Reviews by other divisions, such as Planning, Engineering, or Fire, may
Je
result in additional comments.. 'm ,wpc1 , l°lam k
On the Residential Building Permit Application: C7,I l
1. Project Valuation — Indicate the estimated cost of the proposed work per ECDC 19.70.015.
The amount is required to properly determine permit fees
On the Residential Building Permit Application Form A:
2. Mechanical — Exhaust Fans (single duct) — Clarify the difference in the number of fans listed
and that of those represented on sheet `A-2' detail 2 — Floor Plan. The amounts should
consistently reflect the number to be installed and is required to properly determine the
mechanical installation portion of the permit fees. -m- 1), Al MD s -- � c,
On sheet A-1:
3. General Notes — Note #1 — Change the code version from `2009' to `20121. 'rif
4. General Notes — Note #2 — Change the wording to include the carbon monoxide installation
requirements in existing dwellings per R315.3. t-
5. General Notes — Note #5 — Change the code section for the stair treads and risers from
`R311.5' to `R311.7' . ),�
6. General Notes — Note #6 — Change the wording for the measuring point above the finished
floor for the emergency escape and rescue opening from "sill ht." to `bottom of clear
opening' per R310.1. V`
7, General Notes — Note #8 — Clarify the reference to section `M1508' for the mechanical
ventilation requirements. There is no section `M1508' in the 2012 IRC.
£ _ a
8. General Notes — Note #8 — Change the code table reference for the minimum required local
exhaust rates for `Kitchens, Bathrooms & laundry rooms' from `M1507.3' to `M1507.4'. "
9. General Notes —Note #10 —Insert the wording "...draftstopping per...' n front of
`R302.12' to differentiate it from `fire blocking' and its requirements.
10. General Notes — Note #I I — Change the code version from `2009' to `2012'.1
1.1. General Notes — Note #13 — Clarify the reference to section `(SRC) 327' for `security'.
Section `R327' regards the requirements for protection against radon. t T1�
12. Structural Notes — Note #2 - Change the seismic design category from `D2' to `D1' per
Table R301.2(1).
13. Structural Notes — Note #9 — Indicate on the plans the fasteners and fastener spacing for the
attachment of the roof sheathing to meet the requirements of R602.3(1) and guide proper
construction and inspection. , t °' �- t M . ,
14. Structural Notes — Note #9 — Indicate on the plans the fasteners and fastener spacing for the
attachment of the floor sheathing to meet the requirements of R602.3(1) and guide proper
construction and inspection. 9A, 01&t, r 1 t ��.
15. Detail 4 — West Elevation — Change the detail number from `4' (or that of the 'East '
Elevation). There appears to be two details numbered `4' on sheet `A-1'.
On sheet A-2:
16. DetaiI 1— Foundation Plan — Indicate on the plans the required size, species, and grade of 2 l
the beam to be used to support the east end of the cantilevered joists below the `Window
Seat' of the `Master Bedroom' to guide proper review, construction, and inspection.
17. Detail 1 — Foundation Plan — Indicate on the plans the required size, species, and grade of , {`
the framing members to be used for the cantilevered joists below the `Window Seat' of the r£ 1 Flag
`Master Bedroom' to guide proper review, construction, and inspection. 11 Tka" i 2 IcD 4P� rl
18. Detail 2 — Floor Plan — Identify on the plans the areas/uses depicted per the City of Edmonds
`Residential Addition/Remodel/Alteration Permit Submittal Requirements. Y-1,
19. Detail 3a — Foundation Detail — Clarify the difference in the required diameter of the anchor .1
bolts specified and that noted in detail `I/A-2' — Foundation Plan — and in note #11 of the 14t
Structural Notes on sheet 'A- I' to guide proper construction and inspection
20. Detail 3a — Foundation Detail — Clarify the difference in the required width of the footing Frac 1 9
specified and that noted in detail `1/A-2' — Foundation Plan — to guide proper construction
and inspection. i Z). b L r i 1 M 1 �CJHI i &4