Loading...
2014-0634 Jantz addition-remodel - LaFon.pdf City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: September 4, 2014 TO: Warren LaFon warrenlafon@earthlink.net FROM: Chuck Miller, Plans Examiner RE: Plan Check: BLD2014-0634 Project: Jantz addition-remodel Project Address: 547 Dayton Street During a review of the plans by the Building Division for the above noted project, it was found that the following information, clarifications, or changes are needed. A complete review cannot be performed until the revised plans/documents, including a written response indicating where the ‘clouded’ or otherwise highlighted changes can be found on the revised plans, have been submitted to a Permit Coordinator. Reviews by other divisions, such as Planning, Engineering, or Fire, may result in additional comments. General note: 1.Separate permits/submittals are required for the following: a)Mechanical b)Plumbing/gas piping c)Fire Alarm d)Fire Sprinkler 2.Provide Washington State Energy Code (WSEC)/Northwest Energy Efficiency Council (NEEC) compliance forms for the following work: a)Building envelope b)Mechanical c)Lighting On sheet A-1: 3.Occupancy a)Clarify on the plans the remaining portion of the structure designated as an ‘S-2’ occupancy. The work represented on the construction documents appears to be converting the existing ‘S-2’ occupancy to other uses. b)Identify on the plans the portion of the structure designated as an ‘A-3’ (meeting room) per IBC 303. 4.Site Plan a)Identify on the plans the ‘new’ space represented at the southeast corner of the structure on sheet ‘A-3’. The exterior walls appear to extend beyond the property lines noted on sheet ‘A-1’. On sheet A-2: 5.Existing Plan – Re-orient the ‘North’ arrow to that accurately indicated on sheet ‘A-3’. On sheet A-3: 6.New First Floor Plan a)Identify on the plans the use of the ‘new’ space added at the southeast corner of the structure. The exterior walls appear to extend beyond the property lines noted on sheet ‘A-1’. b)Identify on the plans the ‘new’ work being done in the area identified as ‘Existing Books’ and the ‘Existing Office’ to the adjacent south. There appears to have been changes in the stair configuration and the removal/addition/relocation of exterior and interior doors from that represented on sheet A-2, beyond that noted in this application for the conversion of the ‘S-2’ occupancy to other uses. c)Indicate on the plans the required 1-hour fire-resistance rated (with exposure from both sides) exterior wall construction for the east and west walls per IBC Table 602. Work done under this permit must maintain the fire-resistance integrity of the walls. d)Indicate on the plans the 1-hour fire-resistance rated construction separating the ‘Meeting Room’ from the remaining areas of the structure per IBC Table 508.4. This includes the west and south walls of and the floor/ceiling above the ‘Meeting Room’. e)Provide a callout to the appropriate detail on sheet ‘A-5’ for the required seismic bracing at the top of the new interior partition walls. f)Indicate on the plans the required ‘panic hardware’ for the doors of the ‘Meeting Room’ per IBC 1008.1.10. The remaining door hardware must be ‘accessible’, and shall not require tight grasping, tight pinching, or twisting of the wrist to operate per IBC 1101.2/1008.1.9.1. g)Provide a detail and a reference to it for the required exterior wall construction for the new and altered portions of the north wall. Include information for the footings/foundation, framing, exterior cladding, and other elements found on a ‘typical wall section’. h)Provide a detail and a reference to it for the required concrete slab floor construction for the new portion of the structure. On sheet A-4: 7.Reflected Ceiling Plan – Provide a detail and a reference to it for the required construction to accommodate sprinkler head penetrations of suspended ceilings without rigid bracing per ASTM E580 section 5.2.8.5/ Northwest Wall and Ceiling Bureau (NWCB) Technical Document 401. Page 2 of 3 On sheet A-5: 8.Meeting Room Kitchen – Indicate on the plans the required accessible components per ICC A117.1-2009: a)Work surface per section 804.3. b)Kitchen sink per section 804.4. c)Appliances per section 804.5. Page 3 of 3