2014-0640 Edmonds Village TI revision - Connell.pdf City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: September 23, 2014 TO: Kendahl Fulkerson kendahlf@connelldesign.com FROM: Chuck Miller, Plans Examiner RE: Plan Check: BLD2014-0640 Project: Edmonds Village TI Project Address: 22001 Hwy 99 During a review of the plans by the Building Division for the above noted project, it was found that the following information, clarifications, or changes are needed. A complete review cannot be performed until the revised plans/documents, including a written response indicating where the ‘clouded’ or otherwise highlighted changes can be found on the revised plans, have been submitted to a Permit Coordinator. Reviews by other divisions, such as Planning, Engineering, or Fire, may result in additional comments. On sheet A1.0: 1.Detail 3 – Section – 2 Hour Rated Wall a.Clarify the required type of fire resistance rated construction to be used to separate ‘Suite #100’ and ‘Suite #200’. Each of the different types listed in Chapter 7 of the IBC (fire walls, fire barriers, fire partitions, etc.) have different purposes and requirements for their placement and construction, such as creating fire areas or separating known occupancies. b.Provide a listed assembly determined in accordance with the test procedures set forth in ASTM E 119 or UL 263 for the ‘2 Hour Rated Wall’ to be constructed between ‘Suite #100’ and ‘Suite #200’ to guide proper review, construction and inspection. It should include the framing member type and their spacing, gypsum wallboard type and ‘offset ‘or ‘stagger’ of layers, required fasteners and their spacing, and other installation criteria.