City of Edmonds
PLAN REVIEW COMMENTS
BUILDING DIVISION
(425) 771-0220
DATE: September 23, 2014
TO: Kendahl Fulkerson
kendahlf@connelldesign.com
FROM: Chuck Miller, Plans Examiner
RE: Plan Check: BLD2014-0640
Project: Edmonds Village TI
Project Address: 22001 Hwy 99
During a review of the plans by the Building Division for the above noted project, it was found that
the following information, clarifications, or changes are needed. A complete review cannot be
performed until the revised plans/documents, including a written response indicating where the
clouded or otherwise highlighted changes can be found on the revised plans, have been submitted
to a Permit Coordinator. Reviews by other divisions, such as Planning, Engineering, or Fire, may
result in additional comments.
On sheet A1.0:
1.Detail 3 Section 2 Hour Rated Wall
a.Clarify the required type of fire resistance rated construction to be used to separate
Suite #100 and Suite #200. Each of the different types listed in Chapter 7 of the
IBC (fire walls, fire barriers, fire partitions, etc.) have different purposes and
requirements for their placement and construction, such as creating fire areas or
separating known occupancies.
b.Provide a listed assembly determined in accordance with the test procedures set forth
in ASTM E 119 or UL 263 for the 2 Hour Rated Wall to be constructed between
Suite #100 and Suite #200 to guide proper review, construction and inspection. It
should include the framing member type and their spacing, gypsum wallboard type
and offset or stagger of layers, required fasteners and their spacing, and other
installation criteria.