2014-0657 Port of Edmonds-Harbor Square mechanical - DK Systems.pdf City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: July 24, 2014 TO: D.K. Systems, Inc. kevin@dksystemsinc.com FROM: Chuck Miller, Plans Examiner RE: Plan Check: BLD2014-0657 Project: Port of Edmonds/Harbor Square mechanical units Project Address: 190 W Dayton Street During a review of the plans by the Building Division for the above noted project, it was found that the following information, clarifications, or changes are needed. A complete review cannot be performed until the revised plans/documents, including a written response indicating where the ‘clouded’ or otherwise highlighted changes can be found on the revised plans, have been submitted to a Permit Coordinator. Reviews by other divisions, such as Planning, Engineering, or Fire, may result in additional comments. On sheet 2: 1.Provide on the plans a detail, designed and ‘stamped’ by an engineer, for the required attachment of rooftop units ‘1’, ‘2’, ‘4’, ‘6’, ‘7’, and ‘8’ per IMC 301.15/17, IBC 1609/1613, and ASCE 7-10 chapter 13. In the provided equipment specifications: 2.Provide equipment performance information for rooftop units ‘1’, ‘2’, ‘4’, ‘6’, ‘7’, and ‘8’, and outdoor heat pumps ‘1’, ‘4’, and ‘5’, indicating compliance with the minimum efficiency requirements of WSEC C403.2.3.