Loading...
2014-0665 Jacobsen's Marine mechanical-gas piping - Right On.pdf City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: July 30, 2014 TO: Right On Heating & Sheet Metal, Inc. rightonheating@frontier.com FROM: Chuck Miller, Plans Examiner RE: Plan Check: BLD2014-0665 Project: Jacobsen’s Marine mechanical-gas piping Project Address: 345 Admiral Way During a review of the plans by the Building Division for the above noted project, it was found that the following information, clarifications, or changes are needed. A complete review cannot be performed until the revised plans/documents, including a written response indicating where the ‘clouded’ or otherwise highlighted changes can be found on the revised plans, have been submitted to a Permit Coordinator. Reviews by other divisions, such as Planning, Engineering, or Fire, may result in additional comments. On sheet A1.0: 1.Indicate on the plans the means to be used for the required attachment of the ‘used-oil furnace’ to resist seismic forces per IMC 301.18. 2.Indicate on the plans the means to be used for the required protection of the ‘used-oil furnace’ from damage per IMC 303.4. 3.Indicate on the plans the means to be used for the required equipment access to the ‘unit- heaters’ per IMC 306.5. Of particular concern are instances where the appliance is placed such that personnel have to climb higher than 16 feet to access it.