Loading...
2014-0745 Chen duplex2 - Munson.pdf City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: November 10, 2014 TO: Randall J. Munson randy.munson@comcast.net FROM: Chuck Miller, Plans Examiner RE: Plan Check: BLD2014-0745 Project: Chen duplex rd Project Address: 21507 73 Place W During a review of the plans by the Building Division for the above noted project, it was found that the following information, clarifications, or changes are needed. A complete review cannot be performed until the revised plans/documents, including a written response indicating where the ‘clouded’ or otherwise highlighted changes can be found on the revised plans, have been submitted to a Permit Coordinator. Reviews by other divisions, such as Planning, Engineering, or Fire, may result in additional comments. Items that recur on this list appear in italics. On sheets A-3 (Unit One Floor Plan) & A-4 (Unit Two Floor Plan): 1.Indicate on both sheets of the plans the following: a.The required egress doors for each unit per R311.2. While the plan review comment response indicates an inability to provide wider entry doors, it appears that doors compliant with R311.2 can be installed as part of the other proposed work for each of the two dwelling units as follows: Unit One – Use ‘French doors’ in the east wall of the ‘Dining Room’ and add · stairs from the deck to the grade below. The stairs must comply with R311.7. Unit Two – Use ‘French doors’ in the east wall of ‘Bedroom 1’. · The building code requires that each dwelling have at least one side-hinged egress door with a minimum clear width of 32 inches when measured between the face of the door and the stop, with the door open 90 degrees. b.The required 1-hour fire-resistance rated wall and floor construction separating each of the dwelling units in the stairway leading to each unit per R302.3. Membrane and through penetrations of the assembly shall be protected per R302.4. The wall and floor construction separating each of the dwelling units are required to be 1-hour fire-resistance rated when tested in accordance with ASTM E 119 or UL 263 and usually require very specific components. Since the structure was not originally built as a two-family dwelling unit, it is unlikely that the required fire resistance can be met with the existing construction; therefore the required components and their installation must be specified to guide proper construction and inspection. c.The means to be used to provide the required heating for each unit per R303.9. Each system and its controls must be separate from that of the other unit. The Snohomish County Assessor’ Office currently indicates that the entire one-family dwelling is heated by a natural gas furnace with a forced-air distribution system. Since the return air portion of the system is prohibited from taking recirculated air from a separate dwelling unit per M1602.2, the existing system can be used for only one of the two dwelling units; therefore the required components and their installation for the other dwelling unit must be specified to guide proper construction and inspection. d.The means to be used to provide the required mechanical ventilation for each unit per M1507.3. Each system and its controls must be separate from that of the other unit. There are four methods of providing the required mechanical ventilation per M1507.3 and since three of them require the presence of a forced-air distribution system, one of them is likely to be used to meet the requirements for one of the dwelling units. Since the existing system can be used for only one of the two dwelling units, the required components and their installation for the other dwelling unit must be specified to guide proper construction and inspection. On sheet A-4: 2.Unit Two Floor Plan a.Indicate on the plans the interior and exterior bearing walls required to be 1-hour (or greater) fire-resistance rated construction for the support of the 1-hour fire- resistance rated floor assembly per R302.3.1. Per prior discussion with the Building Official, the 1-hour fire-resistance rating of the exterior bearing walls may be provided from the interior face of the wall. The floor construction separating each of the dwelling units is required to be supported by walls that are 1-hour fire-resistance rated when tested in accordance with ASTM E 119 or UL 263 and usually require very specific components. Since the structure was not originally built as a two- family dwelling unit, it is unlikely that the required fire resistance can be met with the existing construction; therefore the required components and their installation must be specified to guide proper construction and inspection. b.Clarify the existence of the kitchen, bathroom, and two bedrooms of ‘Unit Two’. The Snohomish County Assessor’s Office lists the existing structure as having 3 bedrooms, 1 full bathroom, and 1 half-bathroom. The scope of work listed on the ‘Residential Building Permit Application’ is the construction of a ‘firewall’ and the ‘replacement of 5 egress windows’, with no change to, or addition of, the plumbing and mechanical systems associated with kitchen and bathrooms. The response to the plan review comment references the measurement of ‘areas’, however the concern is the uses of the square footage, not the amount. The structure was built in 1959 and the area in which it is located was annexed into the City of Edmonds in May of the same year. The records of its construction are provided to the county for tax purposes regardless of the building permit issuing agency. Those records indicate the use of the space as indicated in the prior plan review comment with no record of permits issued for changes since. The scope of work listed on this permit application can be expanded to include the conversion of portions of the existing space into two additional bedrooms, an additional bathroom, and an additional kitchen, along with the required mechanical and plumbing systems associated with kitchens and Page 2 of 3 bathrooms. The size of the deck on the east side of the structure also appears to be different than that noted in other records of the structure. c.Clarify the configuration of the ‘Living Room’, garage, and the location of the laundry. The Snohomish County Assessor’s Office lists the structure as having 672 square feet of basement with a 504 square foot garage. There appears to be the removal/relocation of a wall represented on the plans in the area in question, although no information has been provided regarding the structural provisions necessary in doing so. Again, the response to the plan review comment references the measurement of ‘areas’, while the concern is the uses of the square footage, not the amount. The difference in the square footage of the garage noted in the county records and that represented on the proposed plans appears to indicate a change in the location/addition of walls to convert a portion of the garage into living space with no record of permits issued for such changes. The scope of work listed on this permit application can be expanded to include the conversion of a portion of the existing garage into additional living space along with the required mechanical and plumbing systems associated with the ‘Laundry’. Page 3 of 3