2014-0943 Post Office plumbing - Emerald City-Best.pdf
City of Edmonds
PLAN REVIEW COMMENTS
BUILDING DIVISION
(425) 771-0220
DATE: October 16, 2014
TO: Best Plumbing Group, LLC
cindys.s@bestplumbing.com
FROM: Chuck Miller, Plans Examiner
RE: Plan Check: BLD2014-0943
Project: Post Office plumbing
nd
Project Address: 130 2 Avenue N
During a review of the plans by the Building Division for the above noted project, it was found that
the following information, clarifications, or changes are needed. A complete review cannot be
performed until the revised plans/documents, including a written response indicating where the
clouded or otherwise highlighted changes can be found on the revised plans, have been submitted
to a Permit Coordinator. Reviews by other divisions, such as Planning, Engineering, or Fire, may
result in additional comments.
On sheets P2.00, P2.01, P2.02, P2.03, P2.04, and P2.05:
1.Storm Drain Sizing Note Change the table reference from 11-2 to 1101.7.
On sheet P2.00:
2.Basement Plan
a.Change the square footage noted at the 6 rain leader at gridline B/3.15 from
13775 to 13415.
b.Change the square footage noted at the 6 rain leader at gridline A/2.25 from
16150 to 15790.
c.Clarify the difference in the water supply connection shown and that required and
represented on separately submitted drawings under permit BLD2014-0074. While
it provides adequate supply for the proposed domestic plumbing fixtures, it may not
when also connected to the required fire sprinkler system.
On sheets P2.01, P2.02, P2.03, P2.04, and P2.05:
3.Indicate on the plans the required venting for the plumbing fixtures represented in the
quadrant bounded by gridlines F.25 and 3.1. While some appear to be shown, the
venting of many fixtures, such as those identified in that area as 11, 16, and 17, is not
represented.
On sheet P2.03:
nd
4.2 Floor Plan Change the waste/vent riser identifier at gridline B.5/3 from 2 to 12.
On sheet P2.04:
rd
5.3 Floor Plan Change the waste/vent riser identifier at gridline B.5/3 from 2 to 12.
rd
6.3 Floor Plan Change the water supply riser identifier at gridline B/3.3 from Q to
D.
rd
7.3 Floor Plan Change the water supply riser identifier at gridline B/4.2 from P to F.
On sheet P2.04 and P2.05:
8.Indicate on the plans the venting for the future plumbing fixtures represented on sheets
P2.02 and P2.03 at gridline C/2.5.
On sheet P4.00:
9.Waste and Vent Riser Diagrams
a.Diagram #10 Change the fixtures identified from BA to CW.
b.Diagram # 15 Change the flag note identifier from 3 to 2.
10.Horizontal Wet Venting Notes
a.Note #1 Change the code section from 908.2.1 to 908.2.
b.Note #3 Change the table reference from 10-1 to 1002.2.
c.Note #6 - Change the table references from 7-3 to 702.1 and from 7-5 to
703.2.
11.Trap Arm Notes Change the table reference from 10-1 to 1002.2.
12.Flag Notes Clarify the reference to DWG P4.02, Detail 10 for piping of suds producing
fixtures. Sheet P4.02 could not be found among the submitted construction documents.
Page 2 of 2