PLAN REVIEW COMMENTS
BUILDING DIVISION
(425) 771-0220
DATE: November 19, 2014
TO: David Buck
hgfreedoc@msn.com
FROM: Andrew Gahan, Plans Examiner
RE: Plan Check: BLD2014-1107
Project: Deck Replacement
th
Project Address: 15701 75 Place W.
During a review of the plans by the Building Division for the above noted project, it was found that
the following information, clarifications, or changes are needed. A complete review cannot be
performed until the revised plans/documents, including a written response indicating where the
clouded or otherwise highlighted changes can be found on the revised plans, have been submitted
to a Permit Coordinator. Reviews by other divisions, such as Planning, Engineering, or Fire, may
result in additional comments.
1.Please clarify the size, spacing and embedment of the lag bolts used to install the ledger.
2.Clarify the length of the joists. Are they 12 to the support or to the cantilevered end.
3.Please clarify the layout of the deck framing. The north end of the deck appears to have
framing going in both directions, and there appears to be a double joist propagating from the
corner that is unsupported an its interior end.
4.Verify that blocking was installed between the deck joists above the new 6x10 beam.
5.Please provide the size and length of the fasteners (denoted decking screws) used to fasten
the decking to the joists.
6.Provide the specifications or make/model of the hardware used at the beam/post and post
footing connections.