2014-1121 Vanderhei (Carlstrom).pdf City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: December 1, 2014 TO: Norman Carlstrom, Architect norman@nc.architect.com FROM: Andrew Gahan, Plans Examiner RE: Plan Check: BLD2014-1121 Project: Accessory Building Project Address: 18416 High Street During a review of the plans by the Building Division for the above noted project, it was found that the following information, clarifications, or changes are needed. A complete review cannot be performed until the revised plans/documents, including a written response indicating where the ‘clouded’ or otherwise highlighted changes can be found on the revised plans, have been submitted to a Permit Coordinator. Reviews by other divisions, such as Planning, Engineering, or Fire, may result in additional comments. 1.It appears that both the 2x12 ridge beam and the (2) 2x12 window header supporting the ridge beam are overstressed. Please provide beam calculations for both. 2.The plans show a shear wall schedule, but the shear wall listed is not called out on the structural plan. The structural plan specifies braced wall assemblies. Please remove the shear wall schedule and include details for the prescriptive assemblies specified. 3.Per IRC R403.1.2, a continuous footing is required for exterior braced wall panels in Seismic Zone D2. Please indicate a continuous footing on the plans. 4.Please specify the beam/foundation connection for the north-south floor beam as was specified for the east-west floor beam. 5.Provide the connection specifications between the roof outrigger elements and the ridge beam.