Loading...
20141125151517570.pdfCity of Edmonds BLD20140311 121 5" AVENUE NORTH EDMONDS, WA 98020 - (425) 771-0220 FAX (425) 771-0221 PUBLIC WORK DEPARTMENT Planning - Building - Engineerhig Website: Nvww.ci.edmonds.wa.us Comments in Red below are provided by LDC, Inc. (Matthew Merritt, P.E.) Engineering Plan Review Comments Permit Application #: BLD20140311 Date: November 13,2014 f Project Name/Address: Duffus — 1049 — 8"' Ave S Contact Person/Address, Fax or E-mail: andydufftis@coj-ncast.net Reviewer: JENNIFER LAMBERT Division: ENGINEERING During review of the subject submittal, it was found that the following information, corrections, or clarifications would need to be addressed. All Handouts referred to in these comments can be accessed at our website: www.ci.edmonds.wa.us under City Government / Development Services Department Engineering Division then scroll down to Handouts: 1) A concrete anti -flotation base is required for the grinder pump assembly. a. The proposed grinder pump location does not allow for the concrete base. Please relocate the pump such that the pump, assembly and base are are located within the subject site. b. Please show how the installation of the assembly and base will occur without obtaining a construction easement. l.a,b,c) Lift Unit relocated to be within 15ft c. Please show and note the base on the plans. of house hose -bib. Concrete base shown on plan/profile. 2) The grinder pump shall be located such that the pump is within 15 feef a'- 6T"`­h-o-s"e­`b`ffb­.- a. Please relocate the pump accordingly. R.a,b) Lift Unit relocated - Flose bib spe b. Please show the location of the hose bib on the Civil plan sheet. 3) The plans call out a simplex easyelectric factory prewired basin. Please add a detail of the basin to the plans. for Basin Added to submittal packet._] 4) Please fill out/highlight the Zoeller Pump submittal I pai��e.so that it is clear what is heir installed.) Individual components for F'ump/Lift F'ackagc specified within catalogue 5) Please note the location of the alarm panel that is to be located within the home. r��—ee USEo Lan],-, 6) Please show the location of the red, flashing., alAEta1gmjp,_. Please note that the lam shall _be visible from the nearest public right-of-way. 7,8) Lamp shown on/above Nema 4x Cabinet on fence to 7) Please add a note to the plans that the j)­ffffp —con 8) Please show the location of the NEMA 4X cabinet. Please note that the cabinet must be in direct line of sight from the pump station. 9) Please show the location of the power (crossing) in the profile detail. 9) Power x--inq shown inprofile DATE E-MAILED, 1111312014 PAGE (1) 121 5 AVENUE NORTH EDMONDS, WA 98020 ®(425) 771-0220 FAX (425) 771-0221 Website: www.ei.edmondsma.us PUBLIC WORK DEPARTMENT Planning . Building ^ Engineering Engineering Plan Review Comments 10) Please show how the installation of the force line will occour without the need of obtaining a construction easement. Per the plans it appears that to install the force line would require some trenching on the north property. Lift Unit relocated off northerly property line to avoid proximity. Sewer force line shifted off PL as possible (centered between house and PL where possible) and shown with minimum 2ft offset from PL and 2ft separation from power where most constrained at home NW corner). Note added to plan with input/direction from City of Edmonds Development Review (Jennifer Lambert and Jeanie McCdonnel) indicating use of 6" PVC encacement pipe where power/sewer separation is 2ft, and that ALL construction to be kept on -site - no construction/ installation practices are to cross the northerly property line. Please resubmit 3 copies of the revised plans and associated documents with a written response to each item to a Permit Coordinator. Please contact me at 425-771-0220 ext 1321 or by e-mail at iennifer.lambertkci.edmonds.wa.us if you have specific questions regarding these plan corrections. DATE E-MAILED 11/13/2014 PAGE (2)