2014-1172 Great Kids Academy TI - Detail V.pdf City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: December 8, 2014 TO: Rayka Krumova krumova.r@gmail.com FROM: Chuck Miller, Plans Examiner RE: Plan Check: BLD2014-1172 Project: Great Kids Academy TI th Project Address: 8115 240 Street SW During a review of the plans by the Building Division for the above noted project, it was found that the following information, clarifications, or changes are needed. A complete review cannot be performed until the revised plans/documents, including a written response indicating where the ‘clouded’ or otherwise highlighted changes can be found on the revised plans, have been submitted to a Permit Coordinator. Reviews by other divisions, such as Planning, Engineering, or Fire, may result in additional comments. On sheet T-1: 1.General Notes – Note #1 – Indicate on the plans the change of occupancy from ‘E’ to ‘I-4’. Spaces identified on sheet ‘T-2’ as ‘Infant Room’ and ‘Toddler Room’ implies the use by children less than 2.5 years of age and would require the occupancy to be determined as an ‘I-4’ per 308.6. On sheet T-2: 2.Proposed Floor Plan a.Clarify the difference in the location, size, use, and placement of doors in the spaces noted on the plans and those represented on the reduced (8-1/2x11) ‘Proposed Floor Plan’ provided among the permit submittal documents. The permit documents should consistently represent the proposed work to guide proper review, construction, and inspection. b.Clarify the difference in the anticipated ages of the children using the rooms as identified and of those proposed during the Development Review Committee meeting held on October 2, 2014. Spaces identified as ‘Infant Room’ and ‘Toddler Room’ implies use by children less than 2.5 years of age and would require the occupancy to be determined as an ‘I-4’ per 308.6. Identifying the ages of the children using each of the spaces will also guide proper review. c.Indicate on the plans the occupant load for each of the areas to be used for educational purposes per Table 1004.1.2. d.Indicate on the plans the requirement that the entire structure shall be provided with an automatic sprinkler system per 903.2.6. e.Indicate on the plans the required automatic smoke detection system per 907.2.6.4. f.Indicate on the plans the required second exit or exit access doorway for the ‘Preschool Room’ per 1015.6. g.Indicate of the plans the required clear space per ICC A117.1-2009 section 305 for the sinks in the ‘Pre-K Room’ and the ‘Toddler Room’. h.Indicate on the plans the required accessibility provisions for the restrooms per 3411.7. Existing structures that are not fully compliant are required to budget 20% of the total project cost to meet this requirement. Page 2 of 2