2014-1217 Grey Whale Holdings LLC (Workshop AB2C).pdf City of Edmonds n PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: January 15, 2015 TO: Aaron Bush Workshop AB2C, LLC aaronjessebush@gmail.com FROM: Andrew Gahan, Plans Examiner RE: Plan Check: BLD2014-1217 Project: Remodel/Future Change of Occupancy Project Address: 410 Dayton Street During a review of the plans by the Building Division for the above noted project, it was found that the following information, clarifications, or changes are needed. A complete review cannot be performed until the revised plans/documents, including a written response indicating where the ‘clouded’ or otherwise highlighted changes can be found on the revised plans, have been submitted to a Permit Coordinator. Reviews by other divisions, such as Planning, Engineering, or Fire, may result in additional comments. The items below are based on a plan review of this project as a ‘B Occupancy’ and addresses the Code minimums as such. In addition, this review was performed in anticipation of a future addition to include a change of occupancy from ‘B’ to ‘R-1’. However, it is not possible to guarantee that the present use will convert to any future change of use without revisions, remodeling and/or additional design. Sheet G0.0 1.Provide the area (in square feet) at each level of the structure. Sheet A1.0 2.The new toilet shown in the existing location is inconsistent with the location of that toilet as shown on sheet A1.1. Sheet A1.1 3.Provide a hand rail on both sides of the stairway leading to the lower level per IBC 1009.15. 4.Provide the method of attaining separation between the lower level and the crawlspace at the access point to the crawlspace. 5.Include an exhaust fan within the utility room per IMC Table 403.3. 6.Clarify the use of the lower floor space. For example, will that space include a full kitchen? 7.Verify that the west exterior wall located <4’-0” from the property line will be fire-rated per IBC Table 602. In addition to the detail provided, please provide the listed assembly to be used, and verify that any existing members intended to be retained meet the requirements therein. 8.Provide the listed assemblies (GA File# or UL#) for rated wall and ceiling/floor construction, and verify that the existing members meet the requirements therein. 9.Verify that the door hardware to be used is compliant with IBC 1008.1.9.1 throughout the building. 10.IBC 1029 requires that each sleeping room have an emergency escape and rescue opening (i.e. emergency egress). The current configuration requires travel through the bathroom to the emergency escape route from ‘room 2’. 11.The bathroom attached to ‘room 2’ appears to have the water closet mislabeled as a lavatory. Please clarify. 12.Please confirm that the building includes an accessible entrance per IBC 1105. 13.Fire alarms throughout the building per IBC 907.2.8 should be provided. Page 2 of 2