PLAN REVIEW COMMENTS
BUILDING DIVISION
(425) 771-0220
DATE: January 16, 2015
TO: Layne Beller
layne@providencebuilds.com
FROM: Andrew Gahan, Plans Examiner
RE: Plan Check: BLD2015-0024
Project: Hand Remodel
Project Address: 1008 Olympic Avenue
During a review of the plans by the Building Division for the above noted project, it was found that
the following information, clarifications, or changes are needed. A complete review cannot be
performed until the revised plans/documents, including a written response indicating where the
‘clouded’ or otherwise highlighted changes can be found on the revised plans, have been submitted
to a Permit Coordinator. Reviews by other divisions, such as Planning, Engineering, or Fire, may
result in additional comments.
1.Please provide beam calculations for the proposed beams to replace the existing bearing
elements as well as for the roof rafters to show they are structurally adequate to resist the
required loads.
2.Please indicate on the plans, how the point loads created by the new beams/posts will be
resisted at the foundation level.
3.Indicate on the plans that smoke detectors and carbon monoxide detectors must be installed
per IRC R314 and R315 while remodeling.