2015-0024 Hand (Beller).pdf City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: January 16, 2015 TO: Layne Beller layne@providencebuilds.com FROM: Andrew Gahan, Plans Examiner RE: Plan Check: BLD2015-0024 Project: Hand Remodel Project Address: 1008 Olympic Avenue During a review of the plans by the Building Division for the above noted project, it was found that the following information, clarifications, or changes are needed. A complete review cannot be performed until the revised plans/documents, including a written response indicating where the ‘clouded’ or otherwise highlighted changes can be found on the revised plans, have been submitted to a Permit Coordinator. Reviews by other divisions, such as Planning, Engineering, or Fire, may result in additional comments. 1.Please provide beam calculations for the proposed beams to replace the existing bearing elements as well as for the roof rafters to show they are structurally adequate to resist the required loads. 2.Please indicate on the plans, how the point loads created by the new beams/posts will be resisted at the foundation level. 3.Indicate on the plans that smoke detectors and carbon monoxide detectors must be installed per IRC R314 and R315 while remodeling.