2015-0032 Cedar View Memory Care Facility - LJB Designs3.pdf
City of Edmonds
PLAN REVIEW COMMENTS
BUILDING DIVISION
(425) 771-0220
DATE: December 2, 2015
TO: Edmonds Memory Care, LLC
jeff@rjdevelopmentservices.com
FROM: Chuck Miller, Plans Examiner
RE: Plan Check: BLD2015-0032
Project: Cedar View Memory Care Community
nd
Project Address: 21006 72 Avenue W
During a review of the plans by the Building Division for the above noted project, it was found that
. A complete review cannot be
the following information, clarifications, or changes are needed
performed until the revised plans/documents, including a written response indicating where
the clouded or otherwise highlighted changes can be found on the revised plans, have been
submitted to a Permit Coordinator.
Items that recur on the list appear in italics.
nd
Resubmittals must be made at the Development Services Department on the 2 Floor of City
Hall. Permit Center hours are M, T, Th, & F from 8am-4:30pm. The Permit Center is closed
on Wednesdays.
Reviews by other divisions, such as Planning, Engineering, or Fire, may result in additional
comments.
On sheet A0.0 Cover Sheet:
1.Sheet Index The following changes/additions need to be made to the plans:
Add sheet C8.1 Site, Drainage & Utility Details - to the index.
·
Change sheet numbers M1.1, M2.1, M2.2, M2.3, M2.4, M2.5, M2.6, and
·
M2.7 to M2.1, M2.2, M2.3, M2.4, M2.5, M2.6, M2.7, and M2.9. The
sheet numbers appear to have been changed on the resubmitted documents.
Add sheet M2.8 ¼ Scale Plumbing Plans - to the index.
·
Add sheet E1.0 Electrical Site Plan - to the index
·
Provide sheet E6.0 Oneline Diagram & Panel Schedules Plan
·
Provide sheet E7.0 Panel & Mechanical Schedules Plan
·
On sheet A2.1 Wall Types:
2.Provide on the plans a detail, and a reference to it, for the required top of non-bearing full-
height fire-resistance rated wall construction to minimize/eliminate moment reversal and
its effects on the engineered floor framing systems. Confer with the project engineer/floor
truss engineer/roof truss engineer regarding design accommodations, or the need for
dynamic top of wall framing, at the top of non-bearing full-height walls.
On sheet A2.2 Rated Assembly:
3.Design No. P554 Clarify the callout for the use of the fire resistance rated design for
areas of the roof with less than a 3/12 slope.
On sheet A3.1 First Floor Plan:
4.First Floor Plan
a.Clarify the callout for wall type 2 to be used for the walls between space 103
Mechanical and spaces 102 Work and 104 Toilet. The specified wall does
not appear to contain the required wall insulation per WSEC Table C402.2.
b.Indicate on the plans the required one-hour fire resistance rated fire door/shutter on
the east side of elevator shaft 135 per IBC Table 716.5 and as represented on the
west side (Storage side) of the elevator shaft on sheet A8.5 Elevator Sections
Section 17/A3.1 Wall Section. The door must be automatic-closing per IBC
716.5.9.2.
c.Indicate on the plans the required one-hour fire resistance rated fire doors/shutters on
each side of elevator shaft 136 per IBC Table 716.5. The doors must be automatic-
closing per IBC 716.5.9.2.
On sheet A3.2 Second Floor Plan:
5.Second Floor Plan
a.Indicate on the plans the required one-hour fire resistance rated fire door/shutter on
the west side (Corridor side) of elevator shaft 235 per IBC Table 716.5 and as
represented on the west side of the elevator shaft on sheet A8.5 Elevator Sections
Section 17/A3.1 Wall Section. The door must be automatic-closing per IBC
716.5.9.2.
b.Indicate on the plans the required one-hour fire resistance rated fire door/shutter on
the east side (Dining side) of elevator shaft 236 per IBC Table 716.5. The door
must be automatic-closing per IBC 716.5.9.2.
On sheet A3.3 Third Floor Plan:
6.Third Floor Plan
a.Indicate on the plans the required one-hour fire resistance rated fire door/shutter on
the west side (Corridor side) of elevator shaft 335 per IBC Table 716.5 and as
represented on the west side of the elevator shaft on sheet A8.5 Elevator Sections
Section 17/A3.1 Wall Section. The door must be automatic-closing per IBC
716.5.9.2.
Page 2 of 4
b.Indicate on the plans the required one-hour fire resistance rated fire door/shutter on
the east side (Dining side) of elevator shaft 336 per IBC Table 716.5. The door
must be automatic-closing per IBC 716.5.9.2.
On sheet A3.5 Enlarged Unit Plans:
7.Semi Private Units G-1 & G2 Flr Plans (Accessible) - Change the callout for wall type 5
at the west interior wall of the bathroom to that noted at that location on sheets A3.2 and
A3.3.
On sheet A3.6 Second Floor Enlarged Service Plan:
8.First Floor Enlarged Lobby/Office Area
a.Clarify the callout for wall type 2 to be used for the walls between space 103
Mechanical and spaces 102 Work and 104 Toilet and the walls between
space 105 Elev/Mech and spaces 100 Lobby and 104 Toilet. The
specified wall does not appear to contain the required wall insulation per WSEC
Table C402.2.
b.Indicate on the plans the required one-hour fire resistance rated fire door/shutter on
the east side (Reception/Lobby side) of elevator shaft 135 per IBC Table 716.5.
The door must be automatic-closing per IBC 716.5.9.2.
9.Second Floor Enlarged Service Area
a.Indicate on the plans the required one-hour fire resistance rated fire door/shutter on
the west side (Corridor side) of elevator shaft 235 per IBC Table 716.5. The door
must be automatic-closing per IBC 716.5.9.2.
b.Indicate on the plans the required one-hour fire resistance rated fire door/shutter on
the east side (Dining side) of elevator shaft 236 per IBC Table 716.5. The door
must be automatic-closing per IBC 716.5.9.2.
On sheet A3.7 Third Floor Enlarged Service Plan
10.Third Floor Enlarged Service Area
a.Indicate on the plans the required one-hour fire resistance rated fire door/shutter on
the west side (Corridor side) of elevator shaft 335 per IBC Table 716.5. The door
must be automatic-closing per IBC 716.5.9.2.
b.Indicate on the plans the required one-hour fire resistance rated fire door/shutter on
the east side (Dining side) of elevator shaft 336 per IBC Table 716.5. The door
must be automatic-closing per IBC 716.5.9.2.
On sheet A3.8 Lobby/Activity Enlarged Plan & Elevation:
11.Lobby/Activity Enlarged Plan - Clarify the callout for wall type 2 to be used for the wall
between space 103 Mechanical and space 102 Work. The specified wall does not
appear to contain the required wall insulation per WSEC Table C402.2.
Page 3 of 4
On sheet A7.1 Building Sections:
12.Section B/A3.1 Cross Section - Change the referenced fire-resistance rated floor/ceiling
assembly for the third floor framing at the west corridors from L569 to Assembly F per
rd
the indicated construction on sheet S-3.1 3 Floor Framing Plan.
On sheet A8.5 Elevator Sections:
13.Section 17/A3.1 Wall Section - Indicate on the plans the required one-hour fire resistance
rated fire door/shutter on the east side (Lobby side) of elevator shaft at level 135 per IBC
Table 716.5. The door must be automatic-closing per IBC 716.5.9.2.
14.Section 18/A3.1 Wall Section
a.Indicate on the plans the required one-hour fire resistance rated fire doors/shutters on
each side of elevator shaft at level 136 per IBC Table 716.5. The doors must be
automatic-closing per IBC 716.5.9.2.
b.Indicate on the plans the required one-hour fire resistance rated fire door/shutter on
the east side (Dining side) of elevator shaft 236 per IBC Table 716.5. The door
must be automatic-closing per IBC 716.5.9.2.
c.Indicate on the plans the required one-hour fire resistance rated fire door/shutter on
the east side (Dining side) of elevator shaft 336 per IBC Table 716.5. The door
must be automatic-closing per IBC 716.5.9.2.
Page 4 of 4