City of Edmonds
PLAN REVIEW COMMENTS
BUILDING DIVISION
(425) 771-0220
DATE: January 30, 2015
TO: Brent Minster
bkminster@earthlink.net
FROM: Chuck Miller, Plans Examiner
RE: Plan Check: BLD2015-0043
Project: Channel Marker TI
Project Address: 120 W Dayton Street #D1
During a review of the plans by the Building Division for the above noted project, it was found that
the following information, clarifications, or changes are needed. A complete review cannot be
performed until the revised plans/documents, including a written response indicating where the
clouded or otherwise highlighted changes can be found on the revised plans, have been submitted
to a Permit Coordinator. Reviews by other divisions, such as Planning, Engineering, or Fire, may
result in additional comments. Items that recur on this list appear in italics.
On sheet A-3.1 New Floor Plan:
1.Indicate on the plans the required 1-hour fire-resistance rated wall construction for the
separation of occupancies along the south and west walls by the pool tables per IBC Table
508.4. The walls must be constructed as fire barriers per IBC 707. Include the UL design
number (or equivalent alternative) and the required fasteners and their spacing for the
attachment of the gypsum wallboard to guide proper construction and inspection. The
response to the review comment notes that No new separation wall (is) being built. and
that the Existing structure stays intact.. The wall removed to allow for an area to be used
for pool tables and pull tabs was of 1-hour fire-resistance rated wall construction required
for the separation of different occupancies (A-2 from B). The existing south and west
walls now by the pool tables were only used to separate different tenants, and not previously
required to be 1-hour fire-resistance rated wall construction for the separation of different
occupancies (B from B). The changing of the boundary of the business now requires
that the existing south and west walls by the pool tables to be 1-hour fire-resistance rated
wall construction required for the separation of different occupancies (A-2 from B).
2.Represent on the plans the location and size of the Patio accessed through, and apparently
a component (an egress court/yard) of the required means of egress from, the occupied
interior portion of the structure. If the Patio is to be used for dining/beverage
consumption, a seating plan must be indicated on the plans along with a calculated occupant
load per IBC Table 1004.1.2. If the Patio is enclosed in any way (a fence, guards, etc.), the
enclosure must be represented on the plans along with a door or gate complying with IBC
1008 leading directly to a public way.
3.A Snohomish Health District review is required prior to the operation of the business. A
plan review approval letter is typically required prior to permit issuance, but in this instance
will become a condition of the permit to be completed before obtaining the final building
inspection approval.