Loading...
2015-0142 Cedar View Memory Care Facility mechanical & plumbing - Dumais Romans .pdfOV EDV City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION "I't WIS91� (425) 771-0220 DATE: April 16, 2015 TO: Edmonds Memory Care, LLC jeff@jdevelopmentservices.com FROM: Chuck Miller, Plans Examiner RE: Plan Check: BLD2015-0142 Project: Cedar View Memory Care mechanical & plumbing Project Address: 21006 72 d Avenue W During a review of the plans by the Building Division for the above noted project, it was found that the following information, clarifications, or changes are needed. A complete review cannot be performed until the revised plans/documents, including a written response indicating where the 'clouded' or otherwise highlighted changes can be found on the revised plans, have been submitted to a Permit Coordinator. Reviews by other divisions, such as Planning, Engineering, or Fire, may result in additional comments. General Review Note: 1. Provide on the plans a representation of the complete gas piping system to be installed and its sizing to guide proper review, installation, and inspection. 2. Provide on the plans a representation of the complete storm drainage system to be installed and its sizing. On sheet MI. 1 — Foundation Plumbing Plan: 3. Foundation Plumbing Plan a. Properly orient the 'north arrow' — it presently identifies 'west' as 'north'. b. Specify on the plans the required sizing of the 'rain water leaders' below space '134' — Parking Garage. On sheet M2.1 — Main Floor Plumbing Plan: 4. General Notes — Complete the information provided for the various notes. 5. Plan Notes — Complete the infon-nation provided for the various notes. 6. Main Floor Plumbing Plan a. Properly orient the 'north arrow' — it presently identifies 'west' as 'north'. b. Provide on the plans a 'legend' for the 'numbers -in -a -hexagon' used to identify the various drain and waste branches to guide proper review, installation, and inspection of the required sizing. c. Specify on the plans the required sizing of the 'rain water leaders' above space '134' — Parking Garage. On sheet M2.2 — Second Floor Plumbing Plan: 7. Second Floor Plumbing Plan a. Properly orient the 'north arrow' — it presently identifies 'west' as 'north'. b. Provide on the plans a 'legend' for the 'numbers -in -a -hexagon' used to identify the various drain and waste branches to guide proper review, installation, and inspection of the required sizing. c. Clarify the callout to detail '1/1' for the installation of the area drains in space '266' — Courtyard #1. No such detail could be found among the submitted construction documents. d. Specify on the plans the required sizing of the area drains in space '266' — Courtyard #1. e. Provide on the plans the specifications for the area drains marked 'AD-l' in space '266' — Courtyard #1. No specifications could be found on sheet 'M4.2' — Plumbing Fixture Schedule. f. Specify on the plans the required sizing of the 'rain water leaders' above space '266' — Courtyard #1. g. Change the 1/4 scale plumbing plan reference for spaces '201' and '202' from '8/M2.5' to '7/M2.5 similar' or provide a reference '8/M2.5'. h. Specify on the plans the complete 'item no.' for the shower/tub plumbing fixture to be installed in space '255' — Shower. i. Specify on the plans the complete 'item no.' for the shower/tub plumbing fixture to be installed in space '257' — Tub. j. Clarify the omission of the ice and water dispenser, of the floor sink, and of the floor drain in space '251' — Serving — as represented on sheets 'FS.01' and 'FS.02'. On sheet M2.3 — Third Floor Plumbing Plan: 8. General Notes — Complete the information provided for the various notes. 9. Plan Notes — Complete the information provided for the various notes. 10. Third Floor Plumbing Plan a. Properly orient the 'north arrow' — it presently identifies 'west' as 'north'. b. Provide on the plans a 'legend' for the 'numbers -in -a -hexagon' used to identify the various drain and waste branches to guide proper review, installation, and inspection of the required sizing. c. Clarify the callout to detail '1/1' for the installation of the area drains in space '368' — Courtyard #2. No such detail could be found among the submitted construction documents. d. Specify on the plans the required sizing of the area drains in space '368' — Courtyard #2. e. Provide on the plans the specifications for the area drains marked 'AD-l' in space '368' — Courtyard #2. No specifications could be found on sheet 'M4.2' — Plumbing Fixture Schedule. f. Change the 1/4 scale plumbing plan reference for space '300' from 'I I/M2.6' to 'I O/M2.6'. g. Change the 1/4 scale plumbing plan reference for spaces '30 1' and '302' from '15/M2.6' to '14/M2.6 similar'. Page 2 of 6 h. Change the 1/4 scale plumbing plan reference for spaces '307', '308', '311', '312', '313', '315', '316', '317', '320', and '321' from '10/_N42.6' to 'I UN42.6 similar'. i. Specify on the plans the complete 'item no.' for the shower/tub plumbing fixture to be installed in space '358' — Tub. j. Indicate on the plans the required 'upsizing' of the vent over the south end of space '333' — Corridor. There appears to be a greater number of units on the 2-inch section than that permitted per Uniform Plumbing Code (UPC) Table 703.2. k. Clarify the omission of the ice and water dispenser, of the floor sink, and of the floor drain in space '352' — Serving — as represented on sheets 'FS.01' and 'FS.02'. On sheet M2.4 - 1/4 Scale Plumbing Plans: 11. Detail I — Partial First Floor a. Specify on the plans the required vent sizing for the fixtures/branches represented. b. Clarify the omission of the floor drain in front of the 'Walk -In -Cooler' in space '119' — Kitchen — as represented on sheet 'FS.02'. 12. Detail 2 — Partial Third Floor — Change the detail label from 'Third' to 'Second'. On sheet M2.5 — 1/4Scale Plumbing Plans: 13. General Review Note - Provide on the plans a 'legend' for the 'numbers -in -a -hexagon' used to identify the various drain and waste branches to guide proper review, installation, and inspection of the required sizing. 14. Detail 4 — 1/4Scale Plumbing Plan — Clarify the representation of the '3/4" DHW' and '3/4" DCW' over the door of space '200' and entering the shaft on the east side of space '235' — Elevator. There does not appear to be any fixtures downstream. On sheet M2.6 — 1/4Scale Plumbing Plans: 15. General Review Note - Provide on the plans a 'legend' for the 'numbers -in -a -hexagon' used to identify the various drain and waste branches to guide proper review, installation, and inspection of the required sizing. 16. Detail 10 — 1/4 Scale Plumbing Plan - Indicate on the plans in the shaft on the east side of space '3 3 5' — Elevator - the l- 1/2 inch diameter vent for the waste of spaces '103', '104', and '105'. On sheet M3.1 — First Floor HVAC Plan: 17. First Floor HVAC Plan a. Specify on the plans the complete 'item no.' of the grille to be installed at the origin of the return -air ducts in the following spaces: * '109' — Storage * '118' - Corridor * '12 1' — Employee * '122' — Toilet * '124' - Storage b. Specify on the plans the complete 'item no.' of the diffuser to be installed at the termination of the supply -air duct in space '101' — Reception. Page 3 of 6 c. Indicate on the plans at diffuser 'D—' the specified CFM for the supply -air of furnace 'F- I' to space '10 V —Reception. d. Specify on the plans the means to be used per International Building Code (IBC) 714.3.2 to protect the membrane penetrations for the installation of the recessed fan - forced electric wall heaters marked 'EH-l' and 'EH-2' to maintain the integrity of the required one -hour fire -resistance rated construction of the walls enclosing the interior access stairways '137' and '138' per IBC 1022.5. On sheet M3.2 — Second Floor HVAC Plan: 18. Second Floor HVAC Plan a. Specify on the plans at grille 'G2' the specified CFM for the return -air of furnace 'F- 7' in space '233' — Corridor. b. Specify on the plans at grille 'G2' the specified CFM for the return -air of furnace 'F- 8' in space '233' — Corridor. c. Specify on the plans the complete 'item no.' for the grilles to be installed at the termination of the transfer duct/opening between spaces '256' — Meeting — and '260' - /2 Car (identified as 'Life Station' on sheet 'A3.2' of the provided architectural drawings). d. Indicate on the plans the required 'Type 11' hood for the cooking appliance in space '25 1' — Serving — per International Mechanical Code (IMC) Table 507.2.2. 19. Plan Notes — Provide on the plans the information regarding the installation of the 12 inch - diameter exhaust duct with 'Plan Note' mark W leading to exhaust fan 'EF-7'. On sheet M3.3 — Third Floor HVAC Plan: 20. Third Floor HVAC Plan a. Indicate on the plans the '12/10' outside air duct down to furnace 'F-6' and up to the intake hood located on the roof. b. Indicate on the plans the '20/16' outside air duct down to furnaces 'F-5', 'F-7', 'F-8', and 'F-9' and up to the intake hood located on the roof. c. Eliminate the note 'AC-2 RL/RS UP & DN' over space '35 1' — Mechanical. The proper location appears to be correctly identified in the east wall of space '349' — Storage. d. Eliminate the extraneous callouts for the smoke dampers over space '358' — Tub. e. Indicate on the plans at grille 'G2' the specified CFM for the return -air of rooftop unit 'RT-3' in space '333' — Corridor. f. Specify on the plans the complete 'item no.' for the grilles to be installed at the termination of the transfer duct/opening between spaces '357' — Meeting — and '361' - /2 Trailer (identified as 'Life Station' on sheet 'A3.3' of the provided architectural drawings). g. Indicate on the plans the required 'Type 11' hood for the cooking appliance in space '352' — Serving — per IMC Table 507.2.2. h. Specify on the plans the means to be used to provide the required mechanical exhaust at the specified airflow rate per IMC Table 403.3. i. Indicate on the plans the location of the thermostatic control for rooftop unit 'RT-l'. Page 4 of 6 j. Specify on the plans the means to be used per IBC 714.3.2 to protect the membrane penetrations for the installation of the recessed fan -forced electric wall heaters marked 'EH-4' and 'EH-5' to maintain the integrity of the required one -hour fire - resistance rated construction of the walls enclosing the interior access stairways '337' and '338' per IBC 1022.5. On sheet M3.4 — Mechanical Roof Plan: 21. Mechanical Roof Plan — Indicate on the plans the intake hood for the outside air duct to fumace'F-10'. On sheet M3.5 — 1/4Scale Plans: 22. Detail I — Partial First Floor a. Specify on the plans the complete 'item no.' of the diffusers to be installed at the termination of the makeup -air ducts in space '119' — Kitchen. b. Indicate on the plans at diffusers 'D—' the specified CFM for the makeup -air of unit 'MUA- 1' to space '119' — Kitchen. c. Complete the diagram representing the required installation of the 'Type F hood in space '119' — Kitchen. 23. Detail 5 — Partial Second Floor — Indicate on the plans the means to be used to provide the required minimum outdoor airflow rate per IMC Table 403.3 to the occupied space(s) mechanically ventilated by furnace 'F- 10'. On sheet M3.6 — Sections: 24. Section A a. Change the second floor space identifier from 'Unit C2' to 'Unit A5'. b. Change the second floor space identifier from 'Jan./S.L.' to 'Storage/Serving'. c. Change the third floor space identifier from 'Unit C2' to 'Unit A'. d. Change the second floor space identifier from 'Jan./S.L.' to 'Mechanical/Serving'. e. Specify on the plans the size of the return -air and supply -air ducts for rooftop unit 'RTU- I' over space '333' — Corridor'. On sheet M3.7 — Sections: 25. Section B a. Specify on the plans the complete 'item no.' of the grille to be installed at the origin of the return air duct in space '118' — Corridor. b. Specify on the plans the complete 'item no.' of the grille to be installed at the origin of the exhaust fan duct in space '122' — Toilet. c. Indicate on the plans the required fire damper for the exhaust duct in space '122' — Toilet'. d. Clarify the difference in the CFM of supply -air to be provided to space '124' — Storage — and that indicated at that location on sheet 'M3. 1'. e. Clarify the difference in the CFM of supply -air to be provided to space '361' — Trailer (identified as 'Life Station' on sheet 'A3.3' of the provided architectural drawings) — and that indicated at that location on sheet 'M3.3'. Page 5 of 6 f. Clarify the difference in the CFM of supply -air to be provided to space '353' — Dining — and that indicated at that location on sheet 'M3.3'. g. Clarify the difference in the diameter of the supply -air duct to space '343' — Assembly — and that indicated at that location on sheet 'M3.3'. On sheet M5.1 — Mechanical Details: 26. Detail I — Gas Fired Furnace with Cooling Coils - Clarify the callout to detail 'I I/M5. F for the installation of the gas piping. The referenced detail does not appear to apply. 27. Detail 2 — Clothes Washer Standpipe — Change the code version from '2009' to '2012' (two locations). 28. Detail 3 — Gas Water Heater a. Eliminate the extraneous note 'vent to exterior' near the ball valve of water heater 'GWH- 1'. b. Clarify the callout to detail 'I I/M5. F for the installation of the gas piping. The referenced detail does not appear to apply. On sheet FS.06 — Special Building Conditions Plan: 29. Kitchen Foodservice Special Building Conditions — Change the detail references for the attachment/support of the 'Type I' and 'Type Il' hoods from 'HS/KC.07' to 'HS/FS.07 Page 6 of 6