20150205144515045.pdfENGINEERING-4 February 03, 2015
Chuck Miller, Plans Examiner
City nfEdmonds
1215mAvenue N 2'mRoor
Edmonds, VVA9QO20
RE: Plan Check: BLD2014-1Z45
Project Name: GBH Holdings Remodel
Project Address: 311 Edmonds Street
Dear Chuck,
Itemized below is bur response to the review comments in the January 20, 2015 letter for
the above referenced project. Our response appears inbold.
General Note:
1. Provide ofloor plan for the second level and aroof framing plan per the City of
Edmonds 'Permit Submittal Requirements' k`guide proper review, construction, and
inspection,
The second floor framing plan has been provided unDetail 2of Sheet SZ.land the
roof framing plan has been provided on Detail I of Sheet S22,
Sheet AO.11
Z. Site Plan
Architect to respond,
Architect to respond.
Sheet A8.01
4. Detail 14-2-H/Floor/Ceiling Assembly
Sheet S:1.11
S. HoNovvnSchedule — Provide nnthe plans the requirements for 'Note 4'referenced in
the 'Anchor Bolt' specification column to guide proper review, installation, and
Note 4 has been provided in the Holdown Schedule on Sheet S1.1.
311EdnxondsStApt. —14225.1O
Comment Response #1
February Ol2O15
Page Zof2
Sheet S2.1
6. Detail I — Foundation Plan — Provide on the plans the required dimensions of the isolated footings to
support the loads below each end of the 5-1/8 x 15 GLB over the south portion of space '102' —
Open Office — to guide proper review, construction , and inspection.
7. Detail 2 — Second Floor Framing Plan — Clarify the callout for the 'existing 2x12 @ 16" OC' floor joists
over the west portion used to support the loads from above. They appear to be close to their design
limits using only the uniform dead and live loads of the floor. The loads from any interior walls or
roof loads appear to potentially result in bending failure depending on the placement of those loads.
The existing joists on the West side of the building will remain unchanged from the
existing condition to the proposed condition, Based on Our Calculation of the existing
condition though, the joists were determined to be adequate to support the floor dead
load and live load per the attached calculations. Note that the existing 2 x 12 joists were
assumed to be DF #:I based on our field observations and the age of the building.
Addbiuna|k,the, capamitymfthe simteredjoists has been determined tmbeadequate to
support the floor dead load and live load inaddition tothe load fromnthe bearing wall
above. See the attached calculations and K)etmi|4 onSheet S4.2,
Additional Revisions:
1. The wood columns supporting the g|u|mmnbeams have been changed toHSS 6mtee|
columns |norder 10 provide fire protection. Sep the attached structura|calculations and Detail
2 on SheetS2.1 and Detail 3 on Sheet SM. Refer to the architectural plans for the fire
|fyou have any questions orcomments regarding the responses tothis review please dnnot hesitate hu
Sincerely,
CG Engineering
Dennis Titus, PE, SE