2015-0377 Westgate Portable.pdf City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: April 24, 2015 TO: Matt Finch Email: Finchm@edmonds.wednet.edu FROM: Leif Bjorback, Building Official RE: Plan Check: 2015-0377 Project: Westgate Elementary Portable th Project Address: 9601 220 St SW During review of the plans for the above noted project, it was found that the following information, clarifications or changes are needed. Please provide written responses as to where the changes can be found on the plans, and submit revised plans/documents to a permit coordinator in the Development Services Department. Thank you. 1.Please indicate on the plans that the proposed building is a factory built structure and will be appropriately labeled with L&I approval. 2.Please provide an occupant load for the new classroom. IBC 1004 3.On sheet A2.1 the insulation notes call for R42 in the ceiling. The minimum requirement per WSEC Table C402.2 is R49. 4.Please demonstrate how the unvented rafter bay assembly as shown on the plans meets the exceptions to roof ventilation as in IBC 1203.2 (WS amendments). 5.The plan set provided does not include a foundation plan. Please provide plans and details for the foundation consistent with the calculations provided. Page 1 of 1