2015-0377 Westgate Portable.pdf
City of Edmonds
PLAN REVIEW COMMENTS
BUILDING DIVISION
(425) 771-0220
DATE: April 24, 2015
TO: Matt Finch
Email: Finchm@edmonds.wednet.edu
FROM: Leif Bjorback, Building Official
RE: Plan Check: 2015-0377
Project: Westgate Elementary Portable
th
Project Address: 9601 220 St SW
During review of the plans for the above noted project, it was found that the following information,
clarifications or changes are needed. Please provide written responses as to where the changes can be found
on the plans, and submit revised plans/documents to a permit coordinator in the Development Services
Department. Thank you.
1.Please indicate on the plans that the proposed building is a factory built structure and will be
appropriately labeled with L&I approval.
2.Please provide an occupant load for the new classroom. IBC 1004
3.On sheet A2.1 the insulation notes call for R42 in the ceiling. The minimum requirement per WSEC
Table C402.2 is R49.
4.Please demonstrate how the unvented rafter bay assembly as shown on the plans meets the exceptions
to roof ventilation as in IBC 1203.2 (WS amendments).
5.The plan set provided does not include a foundation plan. Please provide plans and details for the
foundation consistent with the calculations provided.
Page 1 of 1