In response to your letter dated April 27, 2015 we are providing the following information. Below
please find the text of your comments followed by our response in italics.
1. On the site plan, show the locations of the accessible parking stalls as shown on the approved
plans for building permit BLD2013-0149.SBC 1008.1.9.3
17(,4sr,�oose.' [Iiease see revj�ed !"F.0.2 f(,,)r locafi�',7ns of ac.,cessible parkif7g sh,1116,
2. On sheet G.0.0, the project description includes the Kitchen Hood, yet no details have been
provided for the hood or shaft, and we have not received a hood sizing worksheet. Either indicate
the kitchen hood will be under a separate permit or provide the information as required.
Resr)ot7sel- Kitchen hood is under separate Mechar'iical f.)einW,
3. City records show that the type of construction for the building is type VB, not VA. Please indicate
this on sheet A.0.0.
I'lesI)on,se" ("'citistruction tyl,,)o was revi I sect, pleas(') see, sheet A, 0, 0.
4. On the floor plan please distinguish between fixed and non -fixed tables and chairs.
F?espol'lsc"' Flleas('., see iovis(,-0 sheet A,2C.,2, /tr ach"Jition, occulmi"d load cn') sheel A. 0.0 8a�✓als
cooected it fit ig the correct occuj,�)ant lo,,,,icl,
(Continued Next Page)
1326 Fifth Avenue. Suite 400. Seattle Washington 98101 T: (206) 587.7120 F: (206) 587.7122
burgess design I interiors 0 architecture
5. A minimum of 5% of seated and standing dining surfaces must meet the accessibility standards
of ICC A117.1 section 902. Provide notations and dimensions to show compliance with this section.
I BC 1108.2.9.1
F`?er;j)onse'surfaces,)ne accessil.)16 dining surface h3 1)i'ovided i,,)ut of the 12 din
insurfaces, �Adth a 30"" by
48" ceai
i'aix,,(-,° flooi, sf)ace und6i, the table with a roinhoorn knee clearance of 27", phsmse see
A,2C,2,
6. A minimum clearance of 18 inches is required between the Type 1 hood and combustibles (wood
stud wall framing.) Detail G/A.9.1 does not appear to meet any of the exceptions to IMC 507.9 or
the allowable clearance reductions of IMC Table 308.6. Please provide details (and recognized
source) for an approved method for clearance reduction.
Rest)ot is' , Dc,,,tail 631A,R I w�.is ievis'ed wilh a i'c.--Ouced cleat�ance of 6 inches i-ising a triett"Pod with
galvani7ed sheel steel, having a rni17it'Y?U1'17 thickness of .( 36 inch (.6010) (24(,1a), spaced I im,"11
using I inch hqh roetal hat channels, off the combustible assetrit.51y @ 24'o,c,
7. Permanent roof access is required for rooftop equipment on roofs higher than 16 feet as per IMC
306.5. If the roof exceeds the height limit, provide information on the plans showing compliance with
this code section. If the roof does not exceed 16 feet, please advise.
Response: 7-1-te roof access will be 1)tovided under, the shell irpd clore 1,)e nit (rleirt*t # BLD 2014,
0133 1) arid a delbriedsubinitial ac%"ording to deff r 1,-Wief, fl"ie shell and ar(",,hitect frorn
J(,Ons,on Atchitectur(,-,r and Planniqg,